Voltage Distortion from Harmonic Currents and Fault Level

Individual harmonic voltages and voltage THD at a bus from the harmonic currents of a load and the system short-circuit level, assuming an inductive source.

Thermal power plantProcess steam and utilities

Inputs

Examples: Illustrative 415 V, 20 MVA, six-pulse drivesWeak 415 V supply 8 MVA11 kV bus 150 MVA

Accepted: 200 to 800,000 V
Accepted: 0.1 to 100,000 MVA
Accepted: 0.1 to 100,000 A
Accepted: 0 to 100,000 A
Accepted: 0 to 100,000 A
Accepted: 0 to 100,000 A
Accepted: 0 to 100,000 A

Results

V_h = h·X_s·I_h with X_s = V²/S_sc (source reactance rising with frequency). Background distortion and capacitor resonance are ignored: a capacitor bank near a resonant order can multiply these voltages.

5th harmonic voltage4.4925%
7th harmonic voltage3.7737%
11th harmonic voltage2.4709%
13th harmonic voltage2.1025%
Voltage THD6.7044%
Current THD40.206%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 415 V, 20 MVA, six-pulse drives. The inputs, in the units selected above:

InputValue
Bus voltage (line-to-line)415.00 V
Short-circuit level20.000 MVA
Fundamental current500.00 A
5th harmonic current150.00 A
7th harmonic current90.000 A
11th harmonic current40.000 A
13th harmonic current30.000 A

Applying the formula below gives:

ResultValue
5th harmonic voltage2.6955 %
7th harmonic voltage2.2642 %
11th harmonic voltage1.5814 %
13th harmonic voltage1.4017 %
Voltage THD4.1058 %
Current THD36.387 %

Open this example in the calculator and change any input.

Formula

\(X_s = \frac{V^2}{S_{sc}}, \quad V_h = \frac{hX_sI_h}{V/\sqrt3}, \quad THD_V = \sqrt{\sum V_h^2}\)

Variables

Symbol Meaning SI unit
\(V\) Bus voltage (line-to-line) V
\(S_{sc}\) Short-circuit level VA
\(I_1\) Fundamental current A
\(I_5\) 5th harmonic current A
\(I_7\) 7th harmonic current A
\(I_{11}\) 11th harmonic current A
\(I_{13}\) 13th harmonic current A
\(V_5\) 5th harmonic voltage -
\(V_7\) 7th harmonic voltage -
\(V_{11}\) 11th harmonic voltage -
\(V_{13}\) 13th harmonic voltage -
\(THD_V\) Voltage THD -
\(THD_I\) Current THD -

Method and standards

Harmonic voltage.

Where it is used

  • Drive and rectifier connection studies.
  • Comparing filter options.

Common mistakes

  • Ignoring capacitors near resonance.
  • Using line-to-line voltage per phase.

Assumptions and limits

  • Inductive source; no background distortion.

References

  • Harmonic voltage drop across the source reactance

Questions and answers

Why does a weak supply show more voltage distortion?

The same harmonic currents flow through a larger source reactance, giving larger harmonic voltages.

Why do higher orders matter more than their currents suggest?

Reactance grows with frequency, so a small 11th or 13th current still produces a noticeable voltage.

What do the defaults represent?

An illustrative 415 V bus with a 20 MVA fault level feeding six-pulse drives drawing 500 A fundamental with typical 5th, 7th, 11th and 13th currents.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Dugan, McGranaghan, Santoso and Beaty, Electrical Power Systems Quality, 2nd ed. (McGraw-Hill, 2002), ch. 5

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.