Worked example
Example: Illustrative 415 V, 20 MVA, six-pulse drives. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Bus voltage (line-to-line) | 415.00 V |
| Short-circuit level | 20.000 MVA |
| Fundamental current | 500.00 A |
| 5th harmonic current | 150.00 A |
| 7th harmonic current | 90.000 A |
| 11th harmonic current | 40.000 A |
| 13th harmonic current | 30.000 A |
Applying the formula below gives:
| Result | Value |
|---|---|
| 5th harmonic voltage | 2.6955 % |
| 7th harmonic voltage | 2.2642 % |
| 11th harmonic voltage | 1.5814 % |
| 13th harmonic voltage | 1.4017 % |
| Voltage THD | 4.1058 % |
| Current THD | 36.387 % |
Open this example in the calculator and change any input.
Formula
\(X_s = \frac{V^2}{S_{sc}}, \quad V_h = \frac{hX_sI_h}{V/\sqrt3}, \quad THD_V = \sqrt{\sum V_h^2}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V\) | Bus voltage (line-to-line) | V |
| \(S_{sc}\) | Short-circuit level | VA |
| \(I_1\) | Fundamental current | A |
| \(I_5\) | 5th harmonic current | A |
| \(I_7\) | 7th harmonic current | A |
| \(I_{11}\) | 11th harmonic current | A |
| \(I_{13}\) | 13th harmonic current | A |
| \(V_5\) | 5th harmonic voltage | - |
| \(V_7\) | 7th harmonic voltage | - |
| \(V_{11}\) | 11th harmonic voltage | - |
| \(V_{13}\) | 13th harmonic voltage | - |
| \(THD_V\) | Voltage THD | - |
| \(THD_I\) | Current THD | - |
Method and standards
Harmonic voltage.
Where it is used
- Drive and rectifier connection studies.
- Comparing filter options.
Common mistakes
- Ignoring capacitors near resonance.
- Using line-to-line voltage per phase.
Assumptions and limits
- Inductive source; no background distortion.
References
- Harmonic voltage drop across the source reactance
Questions and answers
Why does a weak supply show more voltage distortion?
The same harmonic currents flow through a larger source reactance, giving larger harmonic voltages.
Why do higher orders matter more than their currents suggest?
Reactance grows with frequency, so a small 11th or 13th current still produces a noticeable voltage.
What do the defaults represent?
An illustrative 415 V bus with a 20 MVA fault level feeding six-pulse drives drawing 500 A fundamental with typical 5th, 7th, 11th and 13th currents.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.