Total Demand Distortion and Current THD

Total demand distortion of a load current against maximum demand current, current THD against the fundamental and the short-circuit ratio at the supply point.

Thermal power plantProcess steam and utilitiesChemical and fertiliser

Inputs

Examples: Illustrative six-pulse drive loadLight load, high THDOffice load with triplens

Accepted: 0.1 to 100,000 A
Accepted: 0.1 to 100,000 A
Accepted: 1 to 10,000,000 A
Accepted: 0 to 100,000 A
Accepted: 0 to 100,000 A
Accepted: 0 to 100,000 A
Accepted: 0 to 100,000 A
Accepted: 0 to 100,000 A
Accepted: 0 to 100,000 A

Results

TDD = √(ΣI_h²)/I_L divides by maximum demand current, so a lightly loaded drive with high THD may still have a low TDD. Limits for TDD depend on the short-circuit ratio I_sc/I_L in the harmonic standard the utility applies; enter the orders that matter (add higher orders if measured).

Total harmonic current (rms)164.72A
Total demand distortion18.303%
Current THD27.454%
Short-circuit ratio27.778

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative six-pulse drive load. The inputs, in the units selected above:

InputValue
Fundamental current at measurement600.00 A
Maximum demand current (12-month average)900.00 A
Short-circuit current at the supply point25,000 A
3rd harmonic15.000 A
5th harmonic140.00 A
7th harmonic70.000 A
9th harmonic5.0000 A
11th harmonic40.000 A
13th harmonic28.000 A

Applying the formula below gives:

ResultValue
Total harmonic current (rms)164.72 A
Total demand distortion18.303 %
Current THD27.454 %
Short-circuit ratio27.778

Open this example in the calculator and change any input.

Formula

\(TDD = \frac{\sqrt{\sum_h I_h^2}}{I_L}, \quad THD_I = \frac{\sqrt{\sum_h I_h^2}}{I_1}\)

Variables

Symbol Meaning SI unit
\(I_1\) Fundamental current at measurement A
\(I_L\) Maximum demand current (12-month average) A
\(I_{sc}\) Short-circuit current at the supply point A
\(I_3\) 3rd harmonic A
\(I_5\) 5th harmonic A
\(I_7\) 7th harmonic A
\(I_9\) 9th harmonic A
\(I_{11}\) 11th harmonic A
\(I_{13}\) 13th harmonic A
\(I_H\) Total harmonic current (rms) A
\(TDD\) Total demand distortion -
\(THD_I\) Current THD -
\(I_{sc}/I_L\) Short-circuit ratio -

Method and standards

Demand distortion.

Where it is used

  • Utility harmonic compliance checks.
  • Comparing drive harmonic solutions.

Common mistakes

  • Dividing by the measured fundamental for TDD.
  • Using instantaneous peak demand for I_L.

Assumptions and limits

  • Orders entered dominate; rms values.

References

  • Total demand distortion definition

Questions and answers

Why use TDD instead of THD?

THD rises at light load even though harmonic amps fall; TDD relates harmonic amps to the full demand the system is built for.

What is I_L?

The average of the monthly maximum demand currents over a year, or the design demand for a new plant.

What do the defaults represent?

An illustrative six-pulse drive load: 600 A fundamental, 900 A maximum demand, 25 kA fault current, with typical 5th, 7th, 11th and 13th harmonics.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Dugan, McGranaghan, Santoso and Beaty, Electrical Power Systems Quality, 3rd ed. (McGraw-Hill, 2012)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.