FireCADCalc

Peak Shaving Battery Size and Demand Saving

Battery power and energy to cap a load peak at a target demand from peak, duration and shape, depth of discharge and efficiency, with the demand charge saving.

Thermal power plantProcess steam and utilities

Inputs

Examples: Illustrative 1200 to 1000 kW, 3 hShort spike 30 min, triangularFlat 4 h evening peak

Accepted: 1 to 1,000,000 kW
Accepted: 1 to 1,000,000 kW
Accepted: 0.016667 to 24 h
Accepted: 30 to 100 %
Accepted: 30 to 100 %
Accepted: 50 to 100 %
Accepted: 0 to 100

Results

Energy above the limit = (P_pk − P_lim)·t·k_s; nameplate = energy/(DoD·η_d). Size on the worst day of the billing period, leave margin for forecast error, and check that the battery recharges between peaks.

Battery power rating200.00kW
Energy to shave50.000kWh
Battery nameplate energy59.737kWh
Demand charge saving per year36,000
Storage duration at rated power (h)0.29869

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 1200 to 1000 kW, 3 h. The inputs, in the units selected above:

InputValue
Peak demand1,200.0 kW
Target demand limit1,000.0 kW
Duration of the peak above the limit3.0000 h
Peak shape factor (1 flat, 0.5 triangular)60.000 %
Usable depth of discharge90.000 %
Discharge efficiency (battery and inverter)93.000 %
Demand charge (per kW per month)12.000 -

Applying the formula below gives:

ResultValue
Battery power rating200.00 kW
Energy to shave360.00 kWh
Battery nameplate energy430.11 kWh
Demand charge saving per year28,800
Storage duration at rated power (h)2.1505

Open this example in the calculator and change any input.

Formula

\(P_b = P_{pk} - P_{lim}, \quad E = P_bt\,k_s, \quad C = \frac{E}{DoD\,\eta_d}\)

Variables

Symbol Meaning SI unit
\(P_{pk}\) Peak demand W
\(P_{lim}\) Target demand limit W
\(t\) Duration of the peak above the limit s
\(k_s\) Peak shape factor (1 flat, 0.5 triangular) -
\(DoD\) Usable depth of discharge -
\(\eta_d\) Discharge efficiency (battery and inverter) -
\(c_d\) Demand charge (per kW per month) -
\(P_b\) Battery power rating W
\(E\) Energy to shave J
\(C\) Battery nameplate energy J
\(S\) Demand charge saving per year -
\(C/P_b\) Storage duration at rated power (h) -

Method and standards

Peak shaving.

Where it is used

  • Commercial and industrial battery projects.
  • Demand management planning.

Common mistakes

  • Sizing on an average day.
  • Forgetting recharge time between peaks.

Assumptions and limits

  • Single daily peak; constant efficiency.

References

  • Peak-shaving storage sizing

Questions and answers

Why does peak shape matter?

A short spike needs little energy for its power; a long flat peak needs much more energy for the same power reduction.

Does peak shaving pay?

Where demand charges are high and peaks are short and predictable; savings are lost if the battery is empty when the monthly peak arrives.

What do the defaults represent?

An illustrative site peaking at 1,200 kW, capped at 1,000 kW over a 3-hour peak of shape factor 0.6, 90 % DoD, 93 % efficiency and a demand charge of 12 per kW-month.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Gilbert Masters, Renewable and Efficient Electric Power Systems (Wiley, 2004), ch. 9

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.