Worked example
Example: Illustrative 4 MWh vanadium 1.6 M. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Energy to store (discharge) | 4,000.0 kWh |
| Active species concentration | 1.6000 mol/L |
| Average discharge cell voltage | 1.4000 V |
| Usable state-of-charge window | 80.000 % |
| Electrons per active ion | 1.0000 - |
| Discharge efficiency (stack and pumps) | 85.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Charge per litre of one electrolyte (Ah/L) | 34.306 |
| Energy density on total electrolyte (Wh/L) | 20.412 |
| Total electrolyte volume | 195.96 m³ |
| Volume of each of the two tanks | 97.982 m³ |
Open this example in the calculator and change any input.
Formula
\(q = nFc\,\Delta SOC, \quad e_{side} = qV\eta_d, \quad V_{tank} = \frac{E}{e_{side}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(E\) | Energy to store (discharge) | J |
| \(c\) | Active species concentration | mol/m³ |
| \(V\) | Average discharge cell voltage | V |
| \(\Delta SOC\) | Usable state-of-charge window | - |
| \(n\) | Electrons per active ion | - |
| \(\eta_d\) | Discharge efficiency (stack and pumps) | - |
| \(q\) | Charge per litre of one electrolyte (Ah/L) | - |
| \(e\) | Energy density on total electrolyte (Wh/L) | - |
| \(V_{tot}\) | Total electrolyte volume | m³ |
| \(V_{tank}\) | Volume of each of the two tanks | m³ |
Method and standards
Flow battery sizing.
Where it is used
- Grid storage design.
- Comparing storage chemistries.
Common mistakes
- Counting both electrolytes in the per-side energy density.
- Ignoring pump and shunt-current losses.
Assumptions and limits
- Average voltage; full use of the SOC window.
References
- Faraday's law for redox flow electrolytes
Questions and answers
Why are flow batteries bulky?
Vanadium electrolyte stores only about 20–25 Wh per litre, roughly a tenth of lithium-ion, so MWh systems need tens of cubic metres of tanks.
What is their advantage?
Energy and power scale separately (tanks versus stacks), the electrolyte does not wear out, and cycle life is very long.
What do the defaults represent?
An illustrative 4 MWh vanadium system: 1.6 mol/L, 1.4 V, 80 % state-of-charge window, one electron and 85 % discharge efficiency.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Gilbert Masters, Renewable and Efficient Electric Power Systems (Wiley, 2004), ch. 9