Worked example
Example: Illustrative heat pump dryer. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Water removed | 40.000 kg/h |
| Compressor power | 10.000 kW |
| Fan power | 3.0000 kW |
| Auxiliary heater power | 0 kW |
| Latent heat of evaporation | 2,400.0 kJ/kg |
| Thermal efficiency of the conventional dryer | 50.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Specific moisture extraction rate (kg per kWh) | 3.0769 |
| Specific energy (kWh per kg) | 0.32500 |
| Conventional dryer, heat per kg (kWh per kg) | 1.3333 |
| Ratio of conventional heat to heat pump electricity | 4.1026 |
| Dryer COP (latent heat removed per electrical energy) | 2.0513 |
Open this example in the calculator and change any input.
Formula
\(SMER = \frac{\dot m_w}{P_c + P_f + P_h}, \quad SEC_c = \frac{\lambda}{\eta_c}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m_w\) | Water removed | kg/s |
| \(P_c\) | Compressor power | W |
| \(P_f\) | Fan power | W |
| \(P_h\) | Auxiliary heater power | W |
| \(\lambda\) | Latent heat of evaporation | J/kg |
| \(\eta_c\) | Thermal efficiency of the conventional dryer | - |
| \(SMER\) | Specific moisture extraction rate (kg per kWh) | - |
| \(SEC\) | Specific energy (kWh per kg) | - |
| \(SEC_c\) | Conventional dryer, heat per kg (kWh per kg) | - |
| \(SEC_c/SEC\) | Ratio of conventional heat to heat pump electricity | - |
| \(COP_{dryer}\) | Dryer COP (latent heat removed per electrical energy) | - |
Method and standards
SMER.
Where it is used
- Food, herb, timber and sludge drying.
- Comparing dryer technologies.
Common mistakes
- Comparing electricity and fuel kWh as if equal in price.
- Omitting fan power.
Assumptions and limits
- Steady operation; latent heat constant.
References
- Specific moisture extraction rate of heat pump dryers
Questions and answers
What SMER is good?
Above about 2 kg/kWh; well-designed units reach 3–4.
Is a heat pump dryer always cheaper to run?
Only if electricity per kWh costs less than its energy advantage times the fuel heat price.
What do the defaults represent?
An illustrative heat pump dryer removing 40 kg/h with a 10 kW compressor and 3 kW fans, against a 50 % efficient hot-air dryer.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Mujumdar (ed.), Handbook of Industrial Drying, 3rd ed. (CRC Press, 2006)