FireCADCalc

Coal Bunker and Fuel Silo Capacity

Bunker or silo volume for a number of hours of firing from the firing rate, bulk density and usable share, split among the bunkers.

Thermal power plantSugar mill and cogenerationPulp and paperBoiler

Inputs

Examples: 12 t/h coal, 12 h, 0.8 t/m³, 85 % usable, 2 bunkersBagasse 25 t/h, 2 h, 0.12 t/m³, 80 % usableIndian coal 50 t/h, 8 h, 0.85 t/m³, 85 %, 4 bunkers

Enter your specification's storage time.
Coal about 0.75–0.9 t/m³; bagasse about 0.1–0.15 t/m³; wood chips about 0.2–0.35 t/m³. Use the value for your fuel.
Allows for the hopper, the angle of repose at the top and dead zones.

Results

Total geometric volume520.83m³
Geometric volume of each bunker520.83m³
Volume of fuel stored416.67m³
Mass of fuel stored50.000t

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 12 t/h coal, 12 h, 0.8 t/m³, 85 % usable, 2 bunkers. The inputs, in the units selected above:

InputValue
Fuel firing rate at MCR12,000 kg/h
Hours of firing to store12.000 h
Bulk density of the fuel800.00 kg/m³
Usable share of the geometric volume85.000 %
Number of bunkers sharing the storage2.0000 -

Applying the formula below gives:

ResultValue
Total geometric volume211.76 m³
Geometric volume of each bunker105.88 m³
Volume of fuel stored180.00 m³
Mass of fuel stored144.00 t

Open this example in the calculator and change any input.

Formula

\(m = \dot m_f\,t_s \qquad V_f = \frac{m}{\rho_b} \qquad V_t = \frac{V_f}{f} \qquad V_1 = \frac{V_t}{n}\)

Variables

Symbol Meaning SI unit
\(\dot m_f\) fuel firing rate at MCR kg/s
\(t_s\) hours of firing to store s
\(\rho_b\) bulk density of the fuel kg/m³
\(f\) usable share of the geometric volume –
\(n\) number of bunkers –
\(V_t\) total geometric volume m³
\(V_1\) geometric volume of each bunker m³
\(V_f\) volume of fuel stored m³
\(m\) mass of fuel stored kg

Method and standards

Mass and volume balance on the bunkers at the MCR firing rate.

Where it is used

  • Sizing coal bunkers and silos for boilers.
  • Setting bunker fill schedules.
  • Checking hours of storage after a fuel change.

Common mistakes

  • Using a coal bulk density that ignores moisture.
  • Counting the whole geometric volume as usable.
  • Ignoring the hopper cone in the volume.

Assumptions and limits

  • Bulk density as stored; wet or fine coal and compacted biomass differ from the loose value.
  • Storage time and usable share are your inputs; the calculator does not suggest them.

References

  • Mass and volume balance

Questions and answers

How big a bunker does a boiler need?

Volume = firing rate × hours ÷ bulk density ÷ usable share. 12 t/h of coal for 12 hours at 0.8 t/m³ is 180 m³ of coal; with 85 % of the bunker usable, 212 m³ in total, 106 m³ each for two bunkers.

Why is bagasse storage so much bigger?

Its bulk density is about one seventh of coal's. Two hours of bagasse at 25 t/h, at a bulk density of 0.12 t/m³ with 80 % of the bin usable, needs about 520 m³ of bin.

What does the usable share cover?

The hopper, the cone of the material at the top (angle of repose) and dead zones that do not flow. Use the share for your bunker shape.

Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.