Spray Pond Area, Nozzles and Make-Up (Hugot)

Spray pond area at Hugot's loading (eqn 40.36), cooled water temperature (40.35), nozzle flow and count (40.40–40.43) and make-up (40.44–40.46).

Sugar mill and cogenerationCondenser and cooling tower

Inputs

Examples: 3 000 m3/h pondHot climate

Hugot: 750 kg/(m²·h); 650–825 in practice.
Hugot: 50–70 %.
Hugot: 3–5 % of the water.

Results

Hugot: pipes 2.5–4 m apart, nozzles 2–2.5 m along them, and margins of 3–4 m windward and 6–8 m leeward. A negative net loss means the condensate added exceeds the losses.

Pond area7,142.9m²
Cooled water temperature38.250°C
Flow per nozzle5.8579m³/h
Number of nozzles854.00
Net loss after condensate gain φ − 1/W2.5000%
Make-up water121.95m³/h

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 3 000 m3/h pond. The inputs, in the units selected above:

InputValue
Warm water to the pond3,000.0 m³/h
Loading750.00 kg/(m²·h)
Warm water temperature50.000 °C
Wet-bulb temperature24.000 °C
Pond efficiency60.000 %
Nozzle discharge coefficient60.000 %
Nozzle area2.3300 cm²
Pressure at the nozzles (head)5.0000 m
Water per kg vapour50.000 -
Losses (evaporation, drift), share of the injection water4.0000 %

Applying the formula below gives:

ResultValue
Pond area4,000.0 m²
Cooled water temperature34.400 °C
Flow per nozzle4.9839 m³/h
Number of nozzles602.00
Net loss after condensate gain φ − 1/W2.0000 %
Make-up water58.824 m³/h

Open this example in the calculator and change any input.

Formula

\(S = \frac{Q_2}{g}, \quad t_1 = t_2 - \rho_e(t_2 - t_0), \quad q = 0.36\,c\,s\sqrt{2gH}\ [\mathrm{m^3/h};\ s\ \mathrm{cm^2}], \quad N = \frac{Q_2}{q}, \quad \varepsilon = \varphi - \frac1W\)

\(N = \left\lceil \frac{Q_2}{q} \right\rceil, \quad E = \max(\varepsilon, 0)\,Q_2\frac{W}{W + 1}\)

Variables

Symbol Meaning SI unit
\(Q_2\) Warm water to the pond m³/s
\(g\) Loading kg/(m²·s)
\(t_2\) Warm water temperature K
\(t_0\) Wet-bulb temperature K
\(\rho_e\) Pond efficiency -
\(c\) Nozzle discharge coefficient -
\(s\) Nozzle area m²
\(H\) Pressure at the nozzles (head) m
\(W\) Water per kg vapour -
\(\varphi\) Losses (evaporation, drift), share of the injection water -
\(S\) Pond area m²
\(t_1\) Cooled water temperature K
\(q\) Flow per nozzle m³/s
\(N\) Number of nozzles -
\(\varepsilon\) Net loss after condensate gain φ − 1/W -
\(E\) Make-up water m³/s

Method and standards

Hugot's spray pond rules.

Where it is used

  • Sizing spray ponds.
  • Water make-up budgets.

Common mistakes

  • Using dry-bulb temperature.
  • Ignoring drift losses in wind.

Assumptions and limits

  • Hugot's loadings from practice.
  • φ and 1/W are shares of the injection water; the warm water Q₂ is the injection water plus condensate, Q₂ = Q_inj(W + 1)/W.
  • Pond efficiency at most 100 %.

References

  • Hugot
  • Handbook of Cane Sugar Engineering
  • 3rd ed. (Elsevier, 1986)
  • ch. 40
  • spray ponds
  • eqns 40.35–40.46
  • pp. 885–890

Questions and answers

What is pond efficiency?

The cooling achieved as a share of the most possible: down to the wet-bulb temperature.

Why does the pond gain water?

The condenser water carries the condensed vapour; 1/W of the flow is added, which offsets part of the losses.

Nozzle pressure?

Hugot: 4–7 m (400–700 g/cm²), about 5 m usual.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.