Worked example
Example: Average air 15 kg/h, 66 cm. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Air to remove | 15.000 kg/h |
| Barometric pressure | 101.33 kPa |
| Vacuum | 66.000 cmHg |
| Injection water | 800.00 m³/h |
Applying the formula below gives:
| Result | Value |
|---|---|
| Approach | 7.8000 K |
| Vapour temperature | 51.549 °C |
| Outlet water temperature | 43.749 °C |
| Water pressure needed (0.1 m per kg/h of air) | 1.5000 m |
Open this example in the calculator and change any input.
Formula
\(H_{76} = 76 - \frac{p_a - H}{1333.224\ \mathrm{Pa/cmHg}}, \quad App = 0.3(10 + R)\frac{79 - H_{76}}{76 - H_{76}}\cdot\frac{4000 - Q_1}{4000}\ [^\circ C;\ R\ \mathrm{kg/h};\ H\ \mathrm{cmHg};\ Q_1\ \mathrm{m^3/h}]\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(R\) | Air to remove | kg/s |
| \(p_a\) | Barometric pressure | Pa |
| \(H\) | Vacuum | Pa |
| \(H_{76}\) | Equivalent vacuum referred to a 76 cmHg barometer | cmHg |
| \(Q_1\) | Injection water | m³/s |
| \(App\) | Approach | K |
| \(t_v\) | Vapour temperature | K |
| \(t_2\) | Outlet water temperature | K |
| \(h_w\) | Water pressure needed (0.1 m per kg/h of air) | m |
Method and standards
Hugot's empirical formula.
Where it is used
- Specifying multi-jet condensers.
- Explaining poor vacuum.
Common mistakes
- Using absolute pressure for H.
- Leaving out air from leaks.
Assumptions and limits
- Multi-jet condensers, normal water.
- Hugot's vacuum is referred to a 76 cmHg barometer, so the vacuum you enter (against your barometer) is turned into the absolute pressure and then into the equivalent vacuum H₇₆ at 76 cm. At sea level the two are the same.
- In the formula R is in kg/h, H in cmHg and Q₁ in m³/h, although the Variables table gives SI units; the page converts.
- The injection water temperature is not an input, so the outlet temperature t₂ is not checked against it; with high air loads it can come out unrealistically low.
References
- Hugot
- Handbook of Cane Sugar Engineering
- 3rd ed. (Elsevier, 1986)
- ch. 40
- jet condensers
- eqn 40.47 and Table 40.21
- pp. 897–900
- Saturation temperature from IAPWS-IF97
Questions and answers
Why does air raise the approach?
Air blankets the water jets and slows condensation; the outgoing water cannot approach the vapour temperature as closely.
Why does the vacuum term rise near 76?
At very high vacuum there is little pressure to drive vapour into the water jets.
Water pressure?
Hugot: about 0.1 m of head per kg/h of air, and 4 m at start-up.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.