Worked example
Example: 3 000 m3/h pond. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Warm water to the pond | 3,000.0 m³/h |
| Loading | 750.00 kg/(m²·h) |
| Warm water temperature | 50.000 °C |
| Wet-bulb temperature | 24.000 °C |
| Pond efficiency | 60.000 % |
| Nozzle discharge coefficient | 60.000 % |
| Nozzle area | 2.3300 cm² |
| Pressure at the nozzles (head) | 5.0000 m |
| Water per kg vapour | 50.000 - |
| Losses (evaporation, drift), share of the injection water | 4.0000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Pond area | 4,000.0 m² |
| Cooled water temperature | 34.400 °C |
| Flow per nozzle | 4.9839 m³/h |
| Number of nozzles | 602.00 |
| Net loss after condensate gain φ − 1/W | 2.0000 % |
| Make-up water | 58.824 m³/h |
Open this example in the calculator and change any input.
Formula
\(S = \frac{Q_2}{g}, \quad t_1 = t_2 - \rho_e(t_2 - t_0), \quad q = 0.36\,c\,s\sqrt{2gH}\ [\mathrm{m^3/h};\ s\ \mathrm{cm^2}], \quad N = \frac{Q_2}{q}, \quad \varepsilon = \varphi - \frac1W\)
\(N = \left\lceil \frac{Q_2}{q} \right\rceil, \quad E = \max(\varepsilon, 0)\,Q_2\frac{W}{W + 1}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q_2\) | Warm water to the pond | m³/s |
| \(g\) | Loading | kg/(m²·s) |
| \(t_2\) | Warm water temperature | K |
| \(t_0\) | Wet-bulb temperature | K |
| \(\rho_e\) | Pond efficiency | - |
| \(c\) | Nozzle discharge coefficient | - |
| \(s\) | Nozzle area | m² |
| \(H\) | Pressure at the nozzles (head) | m |
| \(W\) | Water per kg vapour | - |
| \(\varphi\) | Losses (evaporation, drift), share of the injection water | - |
| \(S\) | Pond area | m² |
| \(t_1\) | Cooled water temperature | K |
| \(q\) | Flow per nozzle | m³/s |
| \(N\) | Number of nozzles | - |
| \(\varepsilon\) | Net loss after condensate gain φ − 1/W | - |
| \(E\) | Make-up water | m³/s |
Method and standards
Hugot's spray pond rules.
Where it is used
- Sizing spray ponds.
- Water make-up budgets.
Common mistakes
- Using dry-bulb temperature.
- Ignoring drift losses in wind.
Assumptions and limits
- Hugot's loadings from practice.
- φ and 1/W are shares of the injection water; the warm water Q₂ is the injection water plus condensate, Q₂ = Q_inj(W + 1)/W.
- Pond efficiency at most 100 %.
References
- Hugot
- Handbook of Cane Sugar Engineering
- 3rd ed. (Elsevier, 1986)
- ch. 40
- spray ponds
- eqns 40.35–40.46
- pp. 885–890
Questions and answers
What is pond efficiency?
The cooling achieved as a share of the most possible: down to the wet-bulb temperature.
Why does the pond gain water?
The condenser water carries the condensed vapour; 1/W of the flow is added, which offsets part of the losses.
Nozzle pressure?
Hugot: 4–7 m (400–700 g/cm²), about 5 m usual.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.