Multijet or Barometric Condenser Injection Water

Injection water for a multijet or barometric condenser from the vapour flow, condenser pressure and water inlet and outlet temperatures (IF97).

Sugar mill and cogenerationDistillery and ethanolIAPWS-IF97 (water and steam)

Inputs

Examples: Pan condenser 16 kPaEvaporator last body

Results

Keep the tail water a few degrees below the vapour temperature; the approach sets the vacuum.

Saturation temperature at condenser pressure60.059°C
Injection water861.29t/h
Water per kg of vapour28.710

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Pan condenser 16 kPa. The inputs, in the units selected above:

InputValue
Vapour to the condenser20.000 t/h
Condenser pressure (absolute)16.000 kPa
Injection water in32.000 °C
Tail water out47.000 °C

Applying the formula below gives:

ResultValue
Saturation temperature at condenser pressure55.314 °C
Injection water766.98 t/h
Water per kg of vapour38.349

Open this example in the calculator and change any input.

Formula

\(\frac{\dot m_w}{\dot m_v} = \frac{h_g(p_c) - h(T_{out})}{h(T_{out}) - h(T_{in})}\)

Variables

Symbol Meaning SI unit
\(\dot m_v\) Vapour to the condenser kg/s
\(p_c\) Condenser pressure (absolute) Pa
\(T_{in}\) Injection water in K
\(T_{out}\) Tail water out K
\(T_s\) Saturation temperature at condenser pressure K
\(\dot m_w\) Injection water kg/s
\(\dot m_w/\dot m_v\) Water per kg of vapour -

Method and standards

Energy balance.

Where it is used

  • Pan and evaporator condensers.
  • Spray pond and cooling tower sizing.

Common mistakes

  • Ignoring the vapour superheat from BPE.

Assumptions and limits

  • Saturated vapour; no air load.
  • The tail water must stay below the vapour saturation temperature; an approach under about 2 K is flagged as unrealistic.

References

  • Energy balance with IAPWS-IF97 enthalpies (saturated vapour, liquid water at 1 atm)

Questions and answers

Why some 30–60 kg of water per kg of vapour?

Each kg of vapour gives about 2400 kJ, while the water warms only 10–20 K; at a 15 K rise it is close to 38 kg.

What limits the outlet temperature?

The vapour saturation temperature at the vacuum needed.

Where does the water go?

To a spray pond or cooling tower and back.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.