FireCADCalc

Condenser Water and Approach by Hugot

Injection water per kg of vapour by Hugot (eqns 40.5–40.6) and by IF97, the outlet temperature by the approach rule and the air partial pressure.

Sugar mill and cogenerationIAPWS-IF97 (water and steam)Condenser and cooling tower

Inputs

Examples: 0.136 kg/cm2, water 30 °CCold water 25 °C, 12 kPa

Hugot: counter-current condensers usually about 0.12; the approach t_v − t₂ never less than 2 °C.

Results

Hugot: keep the water rise t₂ − t₁ to at least 10 °C; the air leaves at about the injection water temperature in a counter-current condenser.

Vapour temperature49.425°C
Water outlet temperature46.983°C
Water per kg vapour, Hugot (607 + 0.3t_v − t₂)/(t₂ − t₁)26.150
Water per kg vapour, mean form 572/(t₂ − t₁)26.020
Water per kg vapour, IF9726.052
Injection water (IF97)521.04t/h
Partial pressure of air at the air outlet (t_a = t₁)8.8336kPa

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 0.136 kg/cm2, water 30 °C. The inputs, in the units selected above:

InputValue
Vapour to condense11,000 kg/h
Condenser pressure (absolute)13.337 kPa
Injection water temperature30.000 °C
Approach factor (t_v − t₂)/(t_v − t₁)12.000 %

Applying the formula below gives:

ResultValue
Vapour temperature51.556 °C
Water outlet temperature48.969 °C
Water per kg vapour, Hugot (607 + 0.3t_v − t₂)/(t₂ − t₁)30.233
Water per kg vapour, mean form 572/(t₂ − t₁)30.154
Water per kg vapour, IF9730.137
Injection water (IF97)331.50 t/h
Partial pressure of air at the air outlet (t_a = t₁)9.0904 kPa

Open this example in the calculator and change any input.

Formula

\(t_2 = t_v - k(t_v - t_1), \quad W_H = \frac{607 + 0.3t_v - t_2}{t_2 - t_1}, \quad W = \frac{h_g(t_v) - h_f(t_2)}{h_f(t_2) - h_f(t_1)}, \quad p_a = p - p_{sat}(t_1)\)

Variables

Symbol Meaning SI unit
\(Q\) Vapour to condense kg/s
\(p\) Condenser pressure (absolute) Pa
\(t_1\) Injection water temperature K
\(k\) Approach factor (t_v − t₂)/(t_v − t₁) -
\(t_v\) Vapour temperature K
\(t_2\) Water outlet temperature K
\(W_H\) Water per kg vapour, Hugot (607 + 0.3t_v − t₂)/(t₂ − t₁) -
\(W_m\) Water per kg vapour, mean form 572/(t₂ − t₁) -
\(W\) Water per kg vapour, IF97 -
\(\dot m_w\) Injection water (IF97) kg/s
\(p_a\) Partial pressure of air at the air outlet (t_a = t₁) Pa

Method and standards

Hugot's condenser heat balance with IF97 enthalpies.

Where it is used

  • Condenser design.
  • Checking injection water pumps.

Common mistakes

  • Using vacuum instead of absolute pressure.
  • Too small a water rise.

Assumptions and limits

  • Counter-current condenser; air leaves at the water inlet temperature.
  • The approach factor must be below 1. Notes flag a water rise below 10 °C or an approach below 2 °C (Hugot).

References

  • Hugot
  • Handbook of Cane Sugar Engineering
  • 3rd ed. (Elsevier, 1986)
  • ch. 40
  • eqns 40.5–40.15
  • pp. 860–866
  • Water and steam enthalpies from IAPWS-IF97

Questions and answers

Why two water figures?

Hugot's formula uses rounded Regnault enthalpies; IF97 gives the exact heat balance. They differ by a few percent.

What is the approach?

How close the outgoing water comes to the vapour temperature; counter-current condensers approach to about 12 % of the range.

Why does the air pressure matter?

The air pump must handle the air at its own partial pressure; colder air is denser and easier to remove.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.