FireCADCalc

Two Identical Fans in Parallel or Series on a System

Operating flow and pressure of one fan, two identical fans in parallel and two in series on one system curve, from a quadratic fan curve and system resistance.

Thermal power plantProcess steam and utilities

Inputs

Examples: Illustrative fan and systemLow-resistance systemHigh-resistance system

Accepted: 1.0197 to 10,197 mmWC
Accepted: 3.6 to 36,000,000 m³/h
Accepted: 0.10197 to 10,197 mmWC
Accepted: 3.6 to 36,000,000 m³/h
Accepted: 0.10197 to 10,197 mmWC

Results

Fan curve p = p₀ − aQ² through shut-off and one point; system p = kQ². Parallel fans share the flow (each at Q/2); series fans add pressure. Parallel helps low-resistance systems, series helps high-resistance ones; neither doubles the flow. Real curves with stall dips can make parallel operation unstable.

Flow with one fan53,666m³/h
Pressure with one fan90.641mmWC
Flow with two in parallel70,265m³/h
Parallel gain1.3093
Flow with two in series60,851m³/h
Series gain1.1339

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative fan and system. The inputs, in the units selected above:

InputValue
Fan shut-off pressure203.94 mmWC
Fan curve point: flow36,000 m³/h
Fan curve point: pressure at Q₁152.96 mmWC
System curve point: flow36,000 m³/h
System curve point: pressure at Q_s142.76 mmWC

Applying the formula below gives:

ResultValue
Flow with one fan36,935 m³/h
Pressure with one fan150.27 mmWC
Flow with two in parallel41,227 m³/h
Parallel gain1.1162
Flow with two in series46,476 m³/h
Series gain1.2583

Open this example in the calculator and change any input.

Formula

\(p = p_0 - aQ^2, \quad Q_{par} = \sqrt{\frac{p_0}{a/4 + k}}, \quad Q_{ser} = \sqrt{\frac{2p_0}{2a + k}}\)

Variables

Symbol Meaning SI unit
\(p_0\) Fan shut-off pressure Pa
\(Q_1\) Fan curve point: flow m³/s
\(p_1\) Fan curve point: pressure at Q₁ Pa
\(Q_s\) System curve point: flow m³/s
\(p_s\) System curve point: pressure at Q_s Pa
\(Q_{one}\) Flow with one fan m³/s
\(p_{one}\) Pressure with one fan Pa
\(Q_{par}\) Flow with two in parallel m³/s
\(Q_{par}/Q_{one}\) Parallel gain -
\(Q_{ser}\) Flow with two in series m³/s
\(Q_{ser}/Q_{one}\) Series gain -

Method and standards

Fan combination.

Where it is used

  • Ventilation and boiler draught systems.
  • Standby and capacity planning.

Common mistakes

  • Assuming flows add in parallel.
  • Ignoring stall regions of fans with unstable curves.

Assumptions and limits

  • Quadratic curves; identical fans; no interaction losses.

References

  • Fan and system curve intersection

Questions and answers

Why doesn't a second fan double the flow?

System resistance rises with the square of flow; the extra fan raises the operating pressure too, so flow increases by much less than double.

When is series better than parallel?

For steep, high-resistance systems; parallel suits flat, low-resistance systems.

What do the defaults represent?

An illustrative fan with 2,000 Pa shut-off and 1,500 Pa at 10 m³/s on a system needing 1,400 Pa at 10 m³/s.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Bleier, Fan Handbook: Selection, Application and Design (McGraw-Hill, 1998)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.