Worked example
Example: Illustrative 0.9 m backward-curved, 40 deg, 12 blades. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Impeller outlet diameter | 0.90000 m |
| Outlet width | 0.15000 m |
| Outlet blade angle from the tangent (90° radial) | 40.000 ° |
| Number of blades | 12.000 - |
| Speed | 1,480.0 rpm |
| Volume flow | 21,600 m³/h |
| Gas density | 1.2000 kg/m³ |
| Hydraulic efficiency | 85.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Tip speed | 69.743 m/s |
| Meridional (radial) velocity at outlet | 14.147 m/s |
| Slip factor | 0.83172 |
| Absolute swirl velocity with slip | 41.147 m/s |
| Euler pressure with slip | 351.16 mmWC |
| Estimated total pressure rise | 298.48 mmWC |
| Pressure coefficient Δp/(ρu₂²) | 0.50148 |
Open this example in the calculator and change any input.
Formula
\(\Delta p_{th} = \rho u_2c_{u2}, \quad c_{u2} = u_2 - c_{m2}\cot\beta_2 - \frac{\pi u_2\sin\beta_2}{z}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(D_2\) | Impeller outlet diameter | m |
| \(b_2\) | Outlet width | m |
| \(\beta_2\) | Outlet blade angle from the tangent (90° radial) | rad |
| \(z\) | Number of blades | - |
| \(n\) | Speed | rad/s |
| \(Q\) | Volume flow | m³/s |
| \(\rho\) | Gas density | kg/m³ |
| \(\eta_h\) | Hydraulic efficiency | - |
| \(u_2\) | Tip speed | m/s |
| \(c_{m2}\) | Meridional (radial) velocity at outlet | m/s |
| \(\sigma\) | Slip factor | - |
| \(c_{u2}\) | Absolute swirl velocity with slip | m/s |
| \(\Delta p_{th}\) | Euler pressure with slip | Pa |
| \(\Delta p\) | Estimated total pressure rise | Pa |
| \(\psi\) | Pressure coefficient Δp/(ρu₂²) | - |
Method and standards
Centrifugal impeller pressure.
Where it is used
- Fan impeller design checks.
- Estimating fan curves.
Common mistakes
- Measuring β₂ from the radial direction.
- Ignoring slip with few blades.
Assumptions and limits
- No inlet swirl; uniform outlet flow.
References
- Euler equation with Stodola slip
Questions and answers
What is slip?
The air leaving the blades does not follow them exactly because of the relative eddy between blades; it leaves with less swirl, reducing pressure by roughly 10–20 %.
Why are backward-curved fans most efficient?
Their blade passages diffuse the flow gently and most pressure rise happens in the impeller, with a non-overloading power curve.
What do the defaults represent?
An illustrative 0.9 m backward-curved wheel (40°, 12 blades, 150 mm wide) at 1,480 rpm moving 6 m³/s of air.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Bleier, Fan Handbook: Selection, Application and Design (McGraw-Hill, 1998)