Worked example
Example: Illustrative 120 kg m2 ID fan, belt drive. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Fan rotor inertia | 120.00 kg·m² |
| Motor rotor inertia | 6.0000 kg·m² |
| Fan speed | 990.00 rpm |
| Motor speed | 1,485.0 rpm |
| Fan shaft power at full speed | 250.00 kW |
| Motor rated power | 315.00 kW |
| Average motor torque during run-up (× rated torque) | 1.6000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Inertia referred to the motor shaft | 59.333 kg·m² |
| Average motor torque | 3,241.0 N·m |
| Fan load torque at full speed (motor shaft) | 1,607.6 N·m |
| Run-up time | 3.5401 s |
| Kinetic energy at speed | 717.43 kJ |
Open this example in the calculator and change any input.
Formula
\(J_{eq} = J_m + J_f\left(\frac{n_f}{n_m}\right)^2, \quad t_a = \frac{J_{eq}}{\sqrt{aT_m}}\tanh^{-1}\left(\omega_m\sqrt{\frac a{T_m}}\right), \quad a = \frac{T_L}{\omega_m^2}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(J_f\) | Fan rotor inertia | kg·m² |
| \(J_m\) | Motor rotor inertia | kg·m² |
| \(n_f\) | Fan speed | rad/s |
| \(n_m\) | Motor speed | rad/s |
| \(P_f\) | Fan shaft power at full speed | W |
| \(P_m\) | Motor rated power | W |
| \(k_T\) | Average motor torque during run-up (× rated torque) | - |
| \(J_{eq}\) | Inertia referred to the motor shaft | kg·m² |
| \(T_m\) | Average motor torque | N·m |
| \(T_L\) | Fan load torque at full speed (motor shaft) | N·m |
| \(t_a\) | Run-up time | s |
| \(E_k\) | Kinetic energy at speed | J |
Method and standards
Run-up time.
Where it is used
- Motor selection for high-inertia fans.
- Checking starting against motor thermal limits.
Common mistakes
- Referring fan inertia without the speed ratio squared.
- Using breakdown torque as the average.
Assumptions and limits
- Constant average motor torque; square-law fan torque.
References
- Rotor acceleration against a square-law load
Questions and answers
Why do large fans need special motors?
Their inertia makes run-up long; the motor's rotor must survive the heat of a long start.
How does a closed damper help?
It cuts the fan's air load during starting, so more motor torque goes into acceleration.
What do the defaults represent?
An illustrative 120 kg·m² fan at 990 rpm belt-driven from a 315 kW, 1,485 rpm motor (6 kg·m²), absorbing 250 kW, motor averaging 1.6 times rated torque.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Jorgensen (ed.), Fan Engineering, 9th ed. (Buffalo Forge / Howden, 1999), Bleier, Fan Handbook: Selection, Application and Design (McGraw-Hill, 1998)