Worked example
Example: Illustrative 1.2 m, hub 0.5 m, 15 m3/s, 600 Pa. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Tip diameter | 1.2000 m |
| Hub diameter | 0.50000 m |
| Speed | 1,480.0 rpm |
| Volume flow | 54,000 m³/h |
| Total pressure rise | 61.183 mmWC |
| Gas density | 1.2000 kg/m³ |
| Hydraulic efficiency | 85.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Axial velocity | 16.049 m/s |
| Blade speed at mean radius | 71.234 m/s |
| Swirl added | 8.2578 m/s |
| Inlet relative flow angle (from the plane of rotation) | 12.697 ° |
| Outlet relative flow angle | 14.297 ° |
| de Haller ratio (keep above about 0.7) | 0.89002 |
Open this example in the calculator and change any input.
Formula
\(\Delta p_t = \eta_h\rho u\Delta c_u, \quad \tan\beta_1 = \frac{c_a}{u}, \quad \tan\beta_2 = \frac{c_a}{u - \Delta c_u}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(D_t\) | Tip diameter | m |
| \(D_h\) | Hub diameter | m |
| \(n\) | Speed | rad/s |
| \(Q\) | Volume flow | m³/s |
| \(\Delta p_t\) | Total pressure rise | Pa |
| \(\rho\) | Gas density | kg/m³ |
| \(\eta_h\) | Hydraulic efficiency | - |
| \(c_a\) | Axial velocity | m/s |
| \(u_m\) | Blade speed at mean radius | m/s |
| \(\Delta c_u\) | Swirl added | m/s |
| \(\beta_1\) | Inlet relative flow angle (from the plane of rotation) | rad |
| \(\beta_2\) | Outlet relative flow angle | rad |
| \(w_2/w_1\) | de Haller ratio (keep above about 0.7) | - |
Method and standards
Axial fan triangles.
Where it is used
- Preliminary axial fan design and blade setting.
- Checking a selection for stall margin.
Common mistakes
- Designing at the tip radius.
- Ignoring the hub's blockage of the flow area.
Assumptions and limits
- No inlet swirl; mean-radius design.
References
- Euler turbomachine equation for axial fans
Questions and answers
Why does the de Haller ratio matter?
It measures how much the relative flow slows through the blade row; too much slowing makes the boundary layer separate and the fan stall.
Why use the root-mean-square radius?
It splits the annulus area in half, so it represents the average blade element reasonably for a first design.
What do the defaults represent?
An illustrative 1.2 m axial fan with a 0.5 m hub at 1,480 rpm moving 15 m³/s against 600 Pa at 85 % hydraulic efficiency.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Bleier, Fan Handbook: Selection, Application and Design (McGraw-Hill, 1998)