Worked example
Example: Illustrative 10 kPa rise, 20 m3/s. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Inlet pressure (absolute) | 101.33 kPa |
| Fan total pressure rise | 1,019.7 mmWC |
| Isentropic exponent | 1.4000 - |
| Inlet volume flow | 72,000 m³/h |
Applying the formula below gives:
| Result | Value |
|---|---|
| Compressibility factor | 0.96662 |
| Air power Q₁ΔpK_p | 193.32 kW |
| Incompressible air power | 200.00 kW |
| Outlet-to-inlet volume ratio (isentropic) | 0.93498 |
Open this example in the calculator and change any input.
Formula
\(K_p = \frac{\kappa}{\kappa - 1}\frac{(1 + x)^{(\kappa - 1)/\kappa} - 1}{x}, \quad x = \frac{\Delta p}{p_1}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(p_1\) | Inlet pressure (absolute) | Pa |
| \(\Delta p\) | Fan total pressure rise | Pa |
| \(\kappa\) | Isentropic exponent | - |
| \(Q_1\) | Inlet volume flow | m³/s |
| \(K_p\) | Compressibility factor | - |
| \(P_u\) | Air power Q₁ΔpK_p | W |
| \(Q_1\Delta p\) | Incompressible air power | W |
| \(Q_2/Q_1\) | Outlet-to-inlet volume ratio (isentropic) | - |
Method and standards
Fan compressibility.
Where it is used
- High-pressure fan and blower sizing.
- Fan test reduction.
Common mistakes
- Using outlet volume flow with inlet-based K_p.
- Applying it to very small pressure rises where it is 1.
Assumptions and limits
- Ideal gas; isentropic reference.
References
- Isentropic work ratio for fans
Questions and answers
When must compressibility be considered?
Above about 2.5 kPa pressure rise (2–3 % density change); for ID fans and blowers the error can reach several per cent.
Why is K_p below 1?
Air is compressed as it passes, so its volume shrinks and less work is needed than incompressible flow at inlet volume would suggest.
What do the defaults represent?
An illustrative 20 m³/s fan with a 10 kPa rise at atmospheric inlet pressure.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Bleier, Fan Handbook: Selection, Application and Design (McGraw-Hill, 1998)