Worked example
Example: Illustrative fan and system. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Fan shut-off pressure | 203.94 mmWC |
| Fan curve point: flow | 36,000 m³/h |
| Fan curve point: pressure at Q₁ | 152.96 mmWC |
| System curve point: flow | 36,000 m³/h |
| System curve point: pressure at Q_s | 142.76 mmWC |
Applying the formula below gives:
| Result | Value |
|---|---|
| Flow with one fan | 36,935 m³/h |
| Pressure with one fan | 150.27 mmWC |
| Flow with two in parallel | 41,227 m³/h |
| Parallel gain | 1.1162 |
| Flow with two in series | 46,476 m³/h |
| Series gain | 1.2583 |
Open this example in the calculator and change any input.
Formula
\(p = p_0 - aQ^2, \quad Q_{par} = \sqrt{\frac{p_0}{a/4 + k}}, \quad Q_{ser} = \sqrt{\frac{2p_0}{2a + k}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(p_0\) | Fan shut-off pressure | Pa |
| \(Q_1\) | Fan curve point: flow | m³/s |
| \(p_1\) | Fan curve point: pressure at Q₁ | Pa |
| \(Q_s\) | System curve point: flow | m³/s |
| \(p_s\) | System curve point: pressure at Q_s | Pa |
| \(Q_{one}\) | Flow with one fan | m³/s |
| \(p_{one}\) | Pressure with one fan | Pa |
| \(Q_{par}\) | Flow with two in parallel | m³/s |
| \(Q_{par}/Q_{one}\) | Parallel gain | - |
| \(Q_{ser}\) | Flow with two in series | m³/s |
| \(Q_{ser}/Q_{one}\) | Series gain | - |
Method and standards
Fan combination.
Where it is used
- Ventilation and boiler draught systems.
- Standby and capacity planning.
Common mistakes
- Assuming flows add in parallel.
- Ignoring stall regions of fans with unstable curves.
Assumptions and limits
- Quadratic curves; identical fans; no interaction losses.
References
- Fan and system curve intersection
Questions and answers
Why doesn't a second fan double the flow?
System resistance rises with the square of flow; the extra fan raises the operating pressure too, so flow increases by much less than double.
When is series better than parallel?
For steep, high-resistance systems; parallel suits flat, low-resistance systems.
What do the defaults represent?
An illustrative fan with 2,000 Pa shut-off and 1,500 Pa at 10 m³/s on a system needing 1,400 Pa at 10 m³/s.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Bleier, Fan Handbook: Selection, Application and Design (McGraw-Hill, 1998)