Worked example
Example: Illustrative 10 m3/s, 1500 Pa, 10 blades, 10 m. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Specific sound power level (from maker or reference data, dB) | 30.000 - |
| Volume flow | 36,000 m³/h |
| Fan pressure | 152.96 mmWC |
| Number of blades | 10.000 - |
| Speed | 1,480.0 rpm |
| Distance from the fan (free field) | 10.000 m |
| Radiation | Hemispherical (on a hard floor) |
Applying the formula below gives:
| Result | Value |
|---|---|
| Sound power level (dB) | 103.52 |
| Blade-passing frequency | 246.67 Hz |
| Sound pressure level at r (dB) | 75.540 |
Open this example in the calculator and change any input.
Formula
\(L_W = L_{Ws} + 10\log_{10}Q + 20\log_{10}\Delta p, \quad f_{BP} = \frac{zn}{60}, \quad L_p = L_W - 10\log_{10}(2\pi r^2)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(L_{Ws}\) | Specific sound power level (from maker or reference data, dB) | - |
| \(Q\) | Volume flow | m³/s |
| \(\Delta p\) | Fan pressure | Pa |
| \(z\) | Number of blades | - |
| \(n\) | Speed | rad/s |
| \(r\) | Distance from the fan (free field) | m |
| \(\text{field}\) | Radiation | - |
| \(L_W\) | Sound power level (dB) | - |
| \(f_{BP}\) | Blade-passing frequency | 1/s |
| \(L_p\) | Sound pressure level at r (dB) | - |
Method and standards
Fan noise estimate.
Where it is used
- Early noise screening of fan selections.
- Silencer requirement estimates.
Common mistakes
- Mixing specific sound power references and units.
- Ignoring duct and room acoustics.
Assumptions and limits
- Specific sound power from data; free-field spreading.
References
- Specific sound power method for fans
Questions and answers
Why does pressure matter more than flow for noise?
Sound power grows with the square of pressure (20 log) but only linearly with flow (10 log); high-pressure fans are noisier.
Where does the tonal noise come from?
Each blade passing the cut-off or a strut makes a pressure pulse at the blade-passing frequency and its harmonics.
What do the defaults represent?
An illustrative 10-blade fan at 1,480 rpm moving 10 m³/s at 1,500 Pa with a specific sound power level of 30 dB, heard at 10 m on a hard floor.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Bleier, Fan Handbook: Selection, Application and Design (McGraw-Hill, 1998)