Impressed-Current CP: Groundbed Resistance and Rectifier Rating

Vertical anode groundbed resistance (Dwight single, Sunde group) and the transformer-rectifier voltage and current for impressed-current CP.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationRefinery and petrochemicalChemical and fertiliserPulp and paper

Inputs

Examples: Five 2 m anodes, 30 Ω·m, 20 ASingle 3 m anode, 100 Ω·m, 5 A

Results

Dwight's formula for one vertical rod and Sunde's for n rods in a line at spacing S. Use the backfill column as the anode size. Keep groundbeds remote from foreign structures to avoid interference.

Single anode resistance17.942Ω
Groundbed resistance17.942Ω
Required voltage94.211V
Rectifier voltage rating113.05V
Rectifier current rating6.0000A
Rectifier d.c. output0.67832kW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Five 2 m anodes, 30 Ω·m, 20 A. The inputs, in the units selected above:

InputValue
Protection current20.000 A
Soil resistivity3.0000e+07 Ω·mm²/m
Anode (backfill column) length2.0000 m
Anode (backfill column) diameter250.00 mm
Number of anodes in line5.0000 -
Anode spacing5.0000 m
Cable and structure-to-earth resistance0.30000 Ω
Back e.m.f.2.0000 V
Design margin on current and voltage25.000 %

Applying the formula below gives:

ResultValue
Single anode resistance7.5413 Ω
Groundbed resistance1.9620 Ω
Required voltage47.240 V
Rectifier voltage rating59.049 V
Rectifier current rating25.000 A
Rectifier d.c. output1.4762 kW

Open this example in the calculator and change any input.

Formula

\(R_1 = \frac{\rho}{2\pi L}\left(\ln\frac{8L}{d} - 1\right), \quad R_n = \frac{\rho}{2\pi nL}\left(\ln\frac{8L}{d} - 1 + \frac{2L}{S}\ln(0.656n)\right), \quad V = I(R_n + R_c) + E_b\)

Variables

Symbol Meaning SI unit
\(I\) Protection current A
\(\rho\) Soil resistivity Ω·m
\(L\) Anode (backfill column) length m
\(d\) Anode (backfill column) diameter m
\(n\) Number of anodes in line -
\(S\) Anode spacing m
\(R_c\) Cable and structure-to-earth resistance Ω
\(E_b\) Back e.m.f. V
\(f_m\) Design margin on current and voltage -
\(R_1\) Single anode resistance Ω
\(R_n\) Groundbed resistance Ω
\(V\) Required voltage V
\(V_r\) Rectifier voltage rating V
\(I_r\) Rectifier current rating A
\(P\) Rectifier d.c. output W

Method and standards

Dwight and Sunde.

Where it is used

  • Pipeline and tank-bottom ICCP design.
  • Plant buried piping protection.

Common mistakes

  • Using anode size instead of backfill column.
  • Close spacing (mutual interference).

Assumptions and limits

  • Uniform soil; vertical anodes in line.
  • Dwight's formula assumes a slender anode: anodes too short for the formula to give a positive resistance are rejected, and a note appears below about ten diameters of length.

References

  • Dwight (1936) single vertical anode and Sunde (1968) multiple anodes in line (Peabody, Control of Pipeline Corrosion, 2nd ed., NACE, ch. 9)

Questions and answers

Why is soil resistivity so important?

Groundbed resistance is proportional to it; high-resistivity sites need more or longer anodes, or deep wells.

What is back e.m.f.?

The galvanic potential between anode and structure that the rectifier must overcome, about 2 V for typical anodes.

What do the defaults represent?

Five 2 m anode columns in 30 Ω·m soil supplying 20 A.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.