Paint Wet and Dry Film Thickness and Coverage

Wet film thickness for a specified dry film from volume solids and thinning, theoretical and practical spreading rates, and the paint volume for an area.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationRefinery and petrochemicalChemical and fertiliserPulp and paper

Inputs

Examples: 75 µm, 60 % VS, 10 % thinner, 500 m²Epoxy 150 µm, 80 % VS, brush

Results

Losses: brush or roller 10–20 %, airless spray 20–40 %, conventional spray on steelwork 40–60 %. Surface profile from blasting also takes paint (about 10–20 µm of DFT equivalent).

Wet film thickness to apply137.50µm
Theoretical spreading rate8.0000m²/L
Practical spreading rate5.6000m²/L
Paint required (unthinned)89.286L

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 75 µm, 60 % VS, 10 % thinner, 500 m². The inputs, in the units selected above:

InputValue
Dry film thickness75.000 µm
Volume solids60.000 %
Thinner added (by volume of paint)10.000 %
Application loss30.000 %
Area to coat500.00 m²

Applying the formula below gives:

ResultValue
Wet film thickness to apply137.50 µm
Theoretical spreading rate8.0000 m²/L
Practical spreading rate5.6000 m²/L
Paint required (unthinned)89.286 L

Open this example in the calculator and change any input.

Formula

\(WFT = \frac{DFT(1 + f_t)}{VS}, \quad TSR = \frac{VS}{DFT}, \quad V = \frac{A}{TSR(1 - f_l)}\)

Variables

Symbol Meaning SI unit
\(DFT\) Dry film thickness m
\(VS\) Volume solids -
\(f_t\) Thinner added (by volume of paint) -
\(f_l\) Application loss -
\(A\) Area to coat m²
\(WFT\) Wet film thickness to apply m
\(TSR\) Theoretical spreading rate (m²/L) -
\(PSR\) Practical spreading rate (m²/L) -
\(V\) Paint required (unthinned) m³

Method and standards

Volume balance.

Where it is used

  • Painting specifications and estimates.
  • Site inspection of coating thickness.

Common mistakes

  • Ignoring application losses.
  • Using weight solids instead of volume solids.

Assumptions and limits

  • Uniform film.
  • The spreading rates are shown in m²/L in every unit system; 1 m²/L = 40.7 ft² per US gallon.

References

  • WFT = DFT(1 + thinner)/VS
  • TSR = 10·VS(%)/DFT(µm) m²/L (coating practice; SSPC PA 2 measurement principle)

Questions and answers

Why measure wet film?

The painter can check wet thickness with a comb gauge as he works; dry film can only be checked later.

Why does thinner raise WFT?

Thinner adds volume but no solids; more wet film is needed for the same dry film.

What do the defaults represent?

A 75 µm coat of a 60 % volume-solids paint thinned 10 %, airless-sprayed on 500 m².

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.