Worked example
Example: Steel coupon 90 days. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Mass loss | 0.052500 g |
| Exposed area | 25.000 cm² |
| Exposure time | 90.000 d |
| Metal density | 7,860.0 kg/m³ |
Applying the formula below gives:
| Result | Value |
|---|---|
| Corrosion rate | 0.010835 mm/a |
| Corrosion rate in mils per year | 0.42659 |
Open this example in the calculator and change any input.
Formula
\(CR = \frac{8.76\times10^4\, W}{A\, T\, D}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(W\) | Mass loss | kg |
| \(A\) | Exposed area | m² |
| \(T\) | Exposure time | s |
| \(\rho\) | Metal density | kg/m³ |
| \(CR\) | Corrosion rate (shown in mm/a) | m/s |
| \(CR_{mpy}\) | Corrosion rate in mils per year | - |
Method and standards
ASTM G1.
Where it is used
- Cooling water and boiler coupon racks.
- Chemical treatment audits.
Common mistakes
- Area of one face only.
- Days for hours.
Assumptions and limits
- Uniform corrosion.
- The ASTM G1 constant 8.76 × 10⁴ uses a 365-day year; the mm/a display uses the Julian year (365.25 d). The two differ by 0.07 %, which is negligible.
References
- ASTM G1: CR = K W/(A T D)
- K = 8.76 × 10⁴ for mm/y with W in g
- A in cm²
- T in h
- D in g/cm³
Questions and answers
52.5 mg lost from 25 cm² of steel in 90 days?
About 0.011 mm/a (0.4 mpy).
Mils per year?
Thousandths of an inch: 1 mm/a ≈ 39.4 mpy.
Cooling water targets?
Your treatment programme sets them; carbon steel often below 0.075 mm/a (3 mpy).