FireCADCalc

Composite Partition Transmission Loss (Wall, Window, Door)

Overall transmission loss of a wall with up to three elements of different areas and transmission losses, by area-weighted transmission coefficients.

Thermal power plantProcess steam and utilitiesChemical and fertiliser

Inputs

Examples: Illustrative wall, window and doorWall with a 1 % open gapEnclosure panel with vision window

Accepted: 0 to 10,000 m²
Accepted: 0 to 100
Accepted: 0 to 10,000 m²
Accepted: 0 to 100
Accepted: 0 to 10,000 m²
Accepted: 0 to 100

Results

τ_i = 10^(−TL_i/10); τ̄ = ΣS_iτ_i/ΣS_i; TL = −10log τ̄. The weakest element dominates: a small door or an open gap (TL ≈ 0) can cut a 50 dB wall to 20 dB. Use each element's TL in the same frequency band.

Average transmission coefficient9.2800e-04
Composite transmission loss30.325
Transmission loss of element 1 alone50.000
Share of sound through element 386.207%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative wall, window and door. The inputs, in the units selected above:

InputValue
Area of element 1 (wall)20.000 m²
Transmission loss 150.000 -
Area of element 2 (window)3.0000 m²
Transmission loss 230.000 -
Area of element 3 (door or gap)2.0000 m²
Transmission loss 320.000 -

Applying the formula below gives:

ResultValue
Average transmission coefficient9.2800e-04
Composite transmission loss30.325
Transmission loss of element 1 alone50.000
Share of sound through element 386.207 %

Open this example in the calculator and change any input.

Formula

\(TL_c = -10\log_{10}\frac{\sum S_i10^{-TL_i/10}}{\sum S_i}\)

Variables

Symbol Meaning SI unit
\(S_1\) Area of element 1 (wall) m²
\(TL_1\) Transmission loss 1 -
\(S_2\) Area of element 2 (window) m²
\(TL_2\) Transmission loss 2 -
\(S_3\) Area of element 3 (door or gap) m²
\(TL_3\) Transmission loss 3 -
\(\bar\tau\) Average transmission coefficient -
\(TL_c\) Composite transmission loss -
\(TL_{1,only}\) Transmission loss of element 1 alone -
\(\eta_3\) Share of sound through element 3 -

Method and standards

Composite TL.

Where it is used

  • Control rooms and enclosures in plants.
  • Building facades and partitions.

Common mistakes

  • Averaging TL values directly.
  • Ignoring ventilation openings.

Assumptions and limits

  • Elements in the same band; diffuse incidence.

References

  • Area-weighted transmission coefficient

Questions and answers

Why does a small gap matter so much?

Sound energy through an opening is not reduced at all, so even 1 % open area limits TL to about 20 dB.

How do I improve a composite wall?

Upgrade the weakest element first: seals on doors, laminated or double glazing, closing gaps.

What do the defaults represent?

An illustrative 20 m² wall of TL 50 with a 3 m² window of TL 30 and a 2 m² door of TL 20.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Bies and Hansen, Engineering Noise Control, 4th ed. (Spon, 2009)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.