Worked example
Example: 1,500 m³ plant room. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Room volume | 1,500.0 m³ |
| Area 1 | 500.00 m² |
| Absorption 1 | 2.0000 % |
| Area 2 | 300.00 m² |
| Absorption 2 | 5.0000 % |
| Area 3 | 300.00 m² |
| Absorption 3 | 10.000 % |
| Area 4 | 0 m² |
| Absorption 4 | 70.000 % |
| Target reverberation time | 1.5000 s |
Applying the formula below gives:
| Result | Value |
|---|---|
| Total absorption (m² sabins) | 55.000 m² |
| Reverberation time | 4.3909 s |
| Extra absorption for the target | 106.00 m² |
| Noise reduction from the extra absorption (dB) | 4.6646 |
Open this example in the calculator and change any input.
Formula
\(A = \sum S_i\alpha_i, \quad T_{60} = \frac{0.161V}{A}, \quad \Delta A = \max\left(\frac{0.161V}{T_t} - A,\ 0\right), \quad \Delta L = 10\log_{10}\frac{A + \Delta A}{A}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V\) | Room volume | m³ |
| \(S_1\) | Area 1 | m² |
| \(\alpha_1\) | Absorption 1 | - |
| \(S_2\) | Area 2 | m² |
| \(\alpha_2\) | Absorption 2 | - |
| \(S_3\) | Area 3 | m² |
| \(\alpha_3\) | Absorption 3 | - |
| \(S_4\) | Area 4 | m² |
| \(\alpha_4\) | Absorption 4 | - |
| \(T_t\) | Target reverberation time | s |
| \(A\) | Total absorption (m² sabins) | m² |
| \(T_{60}\) | Reverberation time | s |
| \(\Delta A\) | Extra absorption for the target | m² |
| \(\Delta L\) | Noise reduction from the extra absorption (dB) | - |
Method and standards
Sabine's equation.
Where it is used
- Control rooms and plant rooms.
- Workshop noise reduction.
Common mistakes
- Using Sabine for very absorbent rooms.
- Single-frequency α for broadband noise.
Assumptions and limits
- Diffuse sound field; average absorption coefficient A/ΣS below about 0.3 (the page warns above it).
- When the room is already deader than the target, ΔA is 0 and the page says so.
References
- Sabine's equation T₆₀ = 0.161V/ΣSα (architectural acoustics)
Questions and answers
Why does absorption lower noise in a plant room?
Reverberant sound builds up from reflections; doubling the absorption lowers the reverberant level by 3 dB.
Does it help close to a machine?
Little: near the source the direct sound dominates; enclosures or barriers are needed there.
What do the defaults represent?
A 1,500 m³ concrete and steel plant room aiming for 1.5 s.