FireCADCalc

Vortex Flowmeter Shedding Frequency (Strouhal)

Vortex shedding frequency behind a bluff body from the flow velocity, bluff body width and Strouhal number, with the K-factor and flow per pulse.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: 50 m³/h in DN80, 22 mm bodySteam 2 m³/s in DN300, 80 mm body, St 0.171 L/s in DN25, 7 mm body

About 0.2 for many bluff bodies over a wide Reynolds range; the meter maker gives the exact value.

Results

Uses the mean pipe velocity; real meters are calibrated, and the blockage of the body raises the local velocity.

Mean velocity in the pipe28.294m/s
Shedding frequency St v / d60.125Hz
Pulses per m³30.063

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 50 m³/h in DN80, 22 mm body. The inputs, in the units selected above:

InputValue
Volume flow50.000 m³/h
Pipe inside diameter77.900 mm
Bluff body width22.000 mm
Strouhal number0.20000 -

Applying the formula below gives:

ResultValue
Mean velocity in the pipe2.9141 m/s
Shedding frequency St v / d26.492 Hz
Pulses per m³1,907.4

Open this example in the calculator and change any input.

Formula

\(f = \frac{St\, v}{d}, \quad K = \frac{f}{Q} = \frac{St}{d\, A}\)

Variables

Symbol Meaning SI unit
\(Q\) Volume flow m³/s
\(D\) Pipe inside diameter m
\(d\) Bluff body width m
\(St\) Strouhal number -
\(v\) Mean velocity in the pipe m/s
\(f\) Shedding frequency St v / d 1/s
\(K\) Pulses per m³ -

Method and standards

Strouhal relation for periodic vortex shedding.

Where it is used

  • Vortex meter range checks.
  • Vibration of pipes and thermowells in flow.

Common mistakes

  • Using pipe diameter for body width.
  • Ignoring the low-flow limit.

Assumptions and limits

  • The mean pipe velocity is used. The real shedding frequency depends on the gap velocity past the body (higher than the pipe mean because of blockage), which the meter's calibrated K-factor includes.

  • No Reynolds-number check: shedding is regular only above a minimum Reynolds number given by the meter maker (typically a few thousand to about 20 000); below it the meter cuts off.

  • Constant Strouhal number.

References

  • Strouhal relation f = St v / d (von Kármán vortex street)

Questions and answers

What frequency at 50 m³/h in DN80 with a 22 mm body?

Velocity 2.91 m/s; frequency 26 Hz.

Why is the K-factor constant?

St is nearly constant over a wide Reynolds range, so frequency is proportional to flow.

What limits low flow?

Below a minimum Reynolds number vortices are irregular.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.