Restriction Orifice Sizing: Liquid or Gas

Bore of a restriction orifice for a liquid at a set pressure drop or for a gas, choked or subcritical, with the cavitation index for liquid service.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationDistillery and ethanolRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: Liquid: 2 kg/s water, 10 bar dropGas: 0.1 kg/s air choked from 20 bar(a)Gas: 0.1 kg/s air, 20 to 15 bar(a), not choked

Gas only. Above the critical pressure p* the flow is subcritical and the bore is sized by the subcritical equation.

Results

Downstream pressure not entered: choked flow is assumed. If the downstream pressure is above p*, enter it; the choked bore would then be too small.

Thin plate, single hole; velocity of approach neglected (small bore relative to pipe). Use several plates in series for large liquid drops.

Orifice bore6.6881mm
Orifice area35.132mm²
Cavitation index (p₁ − p_v)/Δp (liquid)0
Critical downstream pressure (gas)10.566bar

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Liquid: 2 kg/s water, 10 bar drop. The inputs, in the units selected above:

InputValue
ServiceLiquid
Mass flow7,200.0 kg/h
Upstream pressure (absolute)20.000 bar
Pressure drop (liquid)10.000 bar
Liquid density (liquid)998.00 kg/m³
Vapour pressure (liquid)3.1700 kPa
Gas temperature (gas)26.850 °C
Gas molar mass28.960 kg/kmol
Ratio of specific heats1.4000 -
Downstream pressure, absolute (gas; 0 = assume choked)0 bar
Discharge coefficient0.61000 -

Applying the formula below gives:

ResultValue
Orifice bore9.6664 mm
Orifice area73.387 mm²
Cavitation index (p₁ − p_v)/Δp (liquid)1.9968
Critical downstream pressure (gas)0 bar

Open this example in the calculator and change any input.

Formula

\(A = \frac{\dot m}{C_d\sqrt{2\rho\Delta p}}\ \text{(liquid)}, \quad A = \frac{\dot m}{C_dp_1\sqrt{\frac{\gamma}{RT_1}\left(\frac{2}{\gamma + 1}\right)^{\frac{\gamma + 1}{\gamma - 1}}}}\ \text{(choked gas)}\)

\(A = \frac{\dot m}{C_d p_1\sqrt{\frac{2\gamma}{(\gamma - 1)RT_1}\left[\left(\frac{p_2}{p_1}\right)^{2/\gamma} - \left(\frac{p_2}{p_1}\right)^{(\gamma + 1)/\gamma}\right]}}\ \text{(gas, } p_2 > p^*\text{)}, \quad p^* = p_1\left(\frac{2}{\gamma + 1}\right)^{\frac{\gamma}{\gamma - 1}}, \quad R = \frac{R_u}{M}\)

Variables

Symbol Meaning SI unit
\(\text{service}\) Service -
\(\dot m\) Mass flow kg/s
\(p_1\) Upstream pressure (absolute) Pa
\(\Delta p\) Pressure drop (liquid) Pa
\(\rho\) Liquid density (liquid) kg/m³
\(p_v\) Vapour pressure (liquid) Pa
\(T_1\) Gas temperature (gas) K
\(M\) Gas molar mass kg/kmol
\(\gamma\) Ratio of specific heats -
\(p_2\) Downstream pressure, absolute (gas; 0 = assume choked) Pa
\(C_d\) Discharge coefficient -
\(R\) Specific gas constant J/(kg·K)
\(R_u\) Universal gas constant, 8 314.462 618 J/(kmol·K)
\(d\) Orifice bore m
\(A\) Orifice area m²
\(\sigma\) Cavitation index (p₁ − p_v)/Δp (liquid) -
\(p^*\) Critical downstream pressure (gas) Pa

Method and standards

Orifice equation for liquids; isentropic flow of an ideal gas through the orifice for gases, choked when p₂ ≤ p* and subcritical above it.

Where it is used

  • Pump recirculation lines.
  • Purge and vent flow limiting.

Common mistakes

  • Using a metering-orifice C for a restriction plate.
  • Single plate for a flashing drop.

Assumptions and limits

  • Sharp-edged; small β.
  • Gas: if the downstream pressure is left at 0, choked flow is assumed and the page says so; enter p₂ to have subcritical flow sized correctly.
  • The cavitation index of 2 used for the warning is a common screening level, not a limit from a standard; use the plate maker's data for the design.

References

  • Orifice equation (liquid) and critical flow through an orifice (gas) (definitions; Lipták, Instrument Engineers' Handbook, 4th ed. (CRC Press))

Questions and answers

Where are restriction orifices used?

Pump minimum-flow lines, purge and bleed lines, vent limits and fixed pressure letdowns.

Why multi-stage for big drops?

One plate taking a large liquid drop flashes and cavitates; several plates share the drop.

What do the defaults represent?

2 kg/s of water dropping 10 bar from 20 bar(a).

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators