Worked example
Example: Liquid: 2 kg/s water, 10 bar drop. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Service | Liquid |
| Mass flow | 7,200.0 kg/h |
| Upstream pressure (absolute) | 20.000 bar |
| Pressure drop (liquid) | 10.000 bar |
| Liquid density (liquid) | 998.00 kg/m³ |
| Vapour pressure (liquid) | 3.1700 kPa |
| Gas temperature (gas) | 26.850 °C |
| Gas molar mass | 28.960 kg/kmol |
| Ratio of specific heats | 1.4000 - |
| Downstream pressure, absolute (gas; 0 = assume choked) | 0 bar |
| Discharge coefficient | 0.61000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Orifice bore | 9.6664 mm |
| Orifice area | 73.387 mm² |
| Cavitation index (p₁ − p_v)/Δp (liquid) | 1.9968 |
| Critical downstream pressure (gas) | 0 bar |
Open this example in the calculator and change any input.
Formula
\(A = \frac{\dot m}{C_d\sqrt{2\rho\Delta p}}\ \text{(liquid)}, \quad A = \frac{\dot m}{C_dp_1\sqrt{\frac{\gamma}{RT_1}\left(\frac{2}{\gamma + 1}\right)^{\frac{\gamma + 1}{\gamma - 1}}}}\ \text{(choked gas)}\)
\(A = \frac{\dot m}{C_d p_1\sqrt{\frac{2\gamma}{(\gamma - 1)RT_1}\left[\left(\frac{p_2}{p_1}\right)^{2/\gamma} - \left(\frac{p_2}{p_1}\right)^{(\gamma + 1)/\gamma}\right]}}\ \text{(gas, } p_2 > p^*\text{)}, \quad p^* = p_1\left(\frac{2}{\gamma + 1}\right)^{\frac{\gamma}{\gamma - 1}}, \quad R = \frac{R_u}{M}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\text{service}\) | Service | - |
| \(\dot m\) | Mass flow | kg/s |
| \(p_1\) | Upstream pressure (absolute) | Pa |
| \(\Delta p\) | Pressure drop (liquid) | Pa |
| \(\rho\) | Liquid density (liquid) | kg/m³ |
| \(p_v\) | Vapour pressure (liquid) | Pa |
| \(T_1\) | Gas temperature (gas) | K |
| \(M\) | Gas molar mass | kg/kmol |
| \(\gamma\) | Ratio of specific heats | - |
| \(p_2\) | Downstream pressure, absolute (gas; 0 = assume choked) | Pa |
| \(C_d\) | Discharge coefficient | - |
| \(R\) | Specific gas constant | J/(kg·K) |
| \(R_u\) | Universal gas constant, 8 314.462 618 | J/(kmol·K) |
| \(d\) | Orifice bore | m |
| \(A\) | Orifice area | m² |
| \(\sigma\) | Cavitation index (p₁ − p_v)/Δp (liquid) | - |
| \(p^*\) | Critical downstream pressure (gas) | Pa |
Method and standards
Orifice equation for liquids; isentropic flow of an ideal gas through the orifice for gases, choked when p₂ ≤ p* and subcritical above it.
Where it is used
- Pump recirculation lines.
- Purge and vent flow limiting.
Common mistakes
- Using a metering-orifice C for a restriction plate.
- Single plate for a flashing drop.
Assumptions and limits
- Sharp-edged; small β.
- Gas: if the downstream pressure is left at 0, choked flow is assumed and the page says so; enter p₂ to have subcritical flow sized correctly.
- The cavitation index of 2 used for the warning is a common screening level, not a limit from a standard; use the plate maker's data for the design.
References
- Orifice equation (liquid) and critical flow through an orifice (gas) (definitions; Lipták, Instrument Engineers' Handbook, 4th ed. (CRC Press))
Questions and answers
Where are restriction orifices used?
Pump minimum-flow lines, purge and bleed lines, vent limits and fixed pressure letdowns.
Why multi-stage for big drops?
One plate taking a large liquid drop flashes and cavitates; several plates share the drop.
What do the defaults represent?
2 kg/s of water dropping 10 bar from 20 bar(a).
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.