FireCADCalc

Parshall Flume Flow from Upstream Head

Open-channel flow through a Parshall flume from throat width and upstream head under free-flow conditions, with the flume's submergence check.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationDistillery and ethanolRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: 0.6 m flume, 300 mm head1.2 m flume, 450 mm head, 75 % submerged

Results

Submergence above 70 %: the free-flow equation over-reads; apply a submergence correction.

Valid for standard flumes with throat 0.3–2.4 m. Measure H_a at two-thirds of the converging section length upstream of the crest.

Free-flow discharge2,970.0m³/h
Head exponent1.5765
Submergence ratio75.000%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 0.6 m flume, 300 mm head. The inputs, in the units selected above:

InputValue
Throat width600.00 mm
Upstream head300.00 mm
Downstream head (for submergence)120.00 mm

Applying the formula below gives:

ResultValue
Free-flow discharge784.01 m³/h
Head exponent1.5483
Submergence ratio40.000 %

Open this example in the calculator and change any input.

Formula

\(Q = 0.372W\left(\frac{H_a}{0.3048}\right)^{1.569W^{0.026}}\ \ (\mathrm{SI})\)

Variables

Symbol Meaning SI unit
\(W\) Throat width m
\(H_a\) Upstream head m
\(H_b\) Downstream head (for submergence) m
\(Q\) Free-flow discharge m³/s
\(n\) Head exponent -
\(H_b/H_a\) Submergence ratio -

Method and standards

USBR free-flow equation.

Where it is used

  • Effluent treatment plant flow.
  • Cooling water return channels.

Common mistakes

  • Measuring head at the wrong point.
  • Ignoring submergence.

Assumptions and limits

  • Standard Parshall dimensions; free flow.

References

  • Parshall flume free-flow equation Q = 0.372W(H_a/0.3048)^(1.569W^0.026) (US Bureau of Reclamation, Water Measurement Manual)

Questions and answers

Why a flume rather than a weir?

A flume passes solids and loses little head; it suits effluent and irrigation channels.

What is free flow?

When the downstream level is low enough not to back up into the throat; above about 70 % submergence the reading needs correction.

What do the defaults represent?

A 0.6 m flume with 300 mm upstream head.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.