DP Flow Square-Root Extraction and Low-Flow Cut-Off

Flow from a differential pressure transmitter by square-root extraction: flow at a reading, the 4–20 mA signal, and the DP at the low-flow cut-off.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliserISO 5167 (differential-pressure flow)

Inputs

Examples: Quarter of full DP, 5 % cut-offFull scaleLow reading, below the 10 % cut-off

In any flow unit; the result is in the same unit.

Results

At low flow the square root magnifies noise: 1 % of DP is 10 % of flow, hence the cut-off.

Flow at the DP reading50.000
Flow as a share of full scale50.000%
Signal of a linear-DP transmitter8.0000mA
Signal of a square-root (flow) transmitter12.000mA
DP at the low-flow cut-off0.62500mbar

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Quarter of full DP, 5 % cut-off. The inputs, in the units selected above:

InputValue
Flow at full-scale DP100.00 -
Full-scale DP of the transmitter250.00 mbar
DP reading62.500 mbar
Low-flow cut-off (share of full flow)5.0000 %

Applying the formula below gives:

ResultValue
Flow at the DP reading50.000
Flow as a share of full scale50.000 %
Signal of a linear-DP transmitter8.0000 mA
Signal of a square-root (flow) transmitter12.000 mA
DP at the low-flow cut-off0.62500 mbar

Open this example in the calculator and change any input.

Formula

\(Q = Q_{max}\sqrt{\frac{\Delta p}{\Delta p_{max}}}, \quad I_{sqrt} = 4 + 16\,\frac{Q}{Q_{max}}\ \text{mA}, \quad \Delta p_c = q_c^2\, \Delta p_{max}\quad (Q = 0,\ I_{sqrt} = 4\ \text{mA when}\ Q/Q_{max} < q_c)\)

Variables

Symbol Meaning SI unit
\(Q_{max}\) Flow at full-scale DP -
\(\Delta p_{max}\) Full-scale DP of the transmitter Pa
\(\Delta p\) DP reading Pa
\(q_{c}\) Low-flow cut-off (share of full flow) -
\(Q\) Flow at the DP reading -
\(Q/Q_{max}\) Flow as a share of full scale -
\(I_{lin}\) Signal of a linear-DP transmitter A
\(I_{sqrt}\) Signal of a square-root (flow) transmitter A
\(\Delta p_c\) DP at the low-flow cut-off Pa

Method and standards

Flow through a fixed restriction goes as the square root of DP.

Where it is used

  • Configuring DCS and transmitter square-root extraction.
  • Checking flow readings in the field.

Common mistakes

  • Extracting the square root twice (transmitter and DCS).
  • No cut-off at low flow.

Assumptions and limits

  • Constant density and discharge coefficient.
  • Below the low-flow cut-off the flow is shown as zero and the square-root signal as 4 mA; Q/Q_max still gives the uncut share.

References

  • Q ∝ √Δp for differential-pressure flowmeters (ISO 5167-1 principle)

Questions and answers

What flow does a quarter of full-scale DP mean?

Half the full flow: Q = Q_max √(Δp/Δp_max).

What mA does a square-root transmitter give then?

12 mA; a linear-DP transmitter gives 8 mA.

Why a cut-off?

Near zero DP a little noise is a lot of flow; 5 % flow is only 0.25 % of DP.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.