Control Valve Cv and Kv for Liquids (IEC 60534)

Flow coefficient Kv and Cv of a control valve on liquid service by IEC 60534-2-1, with the choked-flow limit for cavitation and flashing.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliserBoilerPump

Inputs

Examples: Feedwater control valve 60 m³/h, 95 to 89 bar(a), 105 °CWater 20 m³/h, 6 to 4 bar(a), 20 °CHot condensate 10 m³/h, 4 to 1.2 bar(a), 140 °C (choked)

Absolute; choose a gauge unit to enter gauge readings.
Water: 2.34 kPa at 20 °C, 1.209 bar at 105 °C, 3.62 bar at 140 °C.
Water 220.64 bar (IAPWS).
From the valve maker; about 0.9 for globe valves, 0.6–0.7 for full-bore ball and butterfly valves.

Results

Flow coefficient Kv (m³/h, bar)14.129
Flow coefficient Cv (US gpm, psi)16.335
Pressure drop across the valve200.00kPa
Choked-flow pressure drop484.19kPa
Pressure drop used for sizing200.00kPa
Liquid critical pressure ratio factor0.95712
Choked (1 = yes)0

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Feedwater control valve 60 m³/h, 95 to 89 bar(a), 105 °C. The inputs, in the units selected above:

InputValue
Volume flow60.000 m³/h
Upstream pressure (absolute)95.000 bar
Downstream pressure (absolute)89.000 bar
Liquid density at the inlet955.00 kg/m³
Vapour pressure at the inlet temperature1.2090 bar
Critical pressure of the liquid220.64 bar
Liquid pressure recovery factor of the valve0.90000 -

Applying the formula below gives:

ResultValue
Flow coefficient Kv (m³/h, bar)23.937
Flow coefficient Cv (US gpm, psi)27.673
Pressure drop across the valve600.00 kPa
Choked-flow pressure drop7,603.0 kPa
Pressure drop used for sizing600.00 kPa
Liquid critical pressure ratio factor0.93927
Choked (1 = yes)0

Open this example in the calculator and change any input.

Formula

IEC 60534-2-1, liquid, turbulent flow, no attached fittings (\(F_P = 1\)):

\(K_v = Q\,\sqrt{\frac{\rho_1/\rho_0}{\Delta p_s}}\ \ (Q\ \text{in m}^3/\text{h},\ \Delta p_s\ \text{in bar},\ \rho_0 = 1000\ \text{kg/m}^3) \qquad C_v = \frac{K_v}{0.865}\)

\(F_F = 0.96 - 0.28\sqrt{\frac{p_v}{p_c}} \qquad \Delta p_{ch} = F_L^2\,(p_1 - F_F\,p_v) \qquad \Delta p = p_1 - p_2 \qquad \Delta p_s = \min(\Delta p,\ \Delta p_{ch})\)

Variables

Symbol Meaning SI unit
\(Q\) volume flow m³/s
\(p_1\) upstream pressure, absolute Pa
\(p_2\) downstream pressure, absolute Pa
\(\rho_1\) liquid density at the inlet kg/m³
\(p_v\) vapour pressure at the inlet temperature Pa
\(p_c\) critical pressure of the liquid Pa
\(F_L\) liquid pressure recovery factor –
\(K_v\) flow coefficient Kv –
\(C_v\) flow coefficient Cv –
\(\Delta p\) pressure drop across the valve Pa
\(\Delta p_{ch}\) choked-flow pressure drop Pa
\(\Delta p_s\) pressure drop used for sizing Pa
\(F_F\) liquid critical pressure ratio factor –
\(\text{choked}\) 1 when the flow is choked –
\(\rho_0\) reference density of water, 1 000 kg/m³

Method and standards

IEC 60534-2-1:2011 §6 for incompressible fluids in turbulent flow, with the numerical constants N₁ of its Table 1 (Kv: 1 with m³/h and bar; Cv: 0.865). The same equations appear in ANSI/ISA-75.01.01.

Where it is used

  • Sizing feedwater, spray water and cooling water control valves.
  • Checking an installed valve for a new duty.
  • Specifying valves for purchase.

Common mistakes

  • Ignoring cavitation and flashing at high pressure drop.
  • Sizing at maximum flow without checking minimum flow controllability.
  • Using the line size as the valve size.

Assumptions and limits

  • Turbulent flow; very viscous liquids need the Reynolds-number factor F_R.
  • No reducers attached to the valve (F_P = 1); with reducers the coefficient rises.
  • F_L from the valve maker for the valve type and opening.
  • ρ₁ and p_v are separate entries: take both at the same inlet temperature (for water, from steam tables); they are not checked against each other.
  • Choked flow means cavitation or flashing: the calculation gives the coefficient; trim selection and noise are the maker's.

References

  • IEC 60534-2-1:2011 (sizing equations for fluid flow)
  • ANSI/ISA-75.01.01

Questions and answers

How do I calculate the Cv of a control valve?

Kv = Q·√((ρ/1000)/Δp), with Q in m³/h and Δp in bar; Cv = Kv/0.865. A feed control valve passing 60 m³/h of 105 °C water with 6 bar drop needs Kv 23.9 (Cv 27.7).

What is choked flow?

Beyond a certain pressure drop the liquid vaporises in the valve and the flow stops increasing. IEC 60534 sets that limit at F_L²(p₁ − F_F·p_v). Hot condensate dropping from 4 to 1.2 bar(a) at 140 °C is choked, and the valve must be sized on the 0.48 bar limit.

Is the valve size the Cv?

No. Choose a valve whose rated Cv is above the one calculated, with the duty in the useful part of its travel, and check the velocities; the maker's sizing program does that.

Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.