FireCADCalc

Tyreus–Luyben Tuning from Ultimate Gain and Period

PI and PID settings by the Tyreus–Luyben rules from the ultimate gain and period (relay or closed-loop test), more conservative than Ziegler–Nichols.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationDistillery and ethanolRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: K_u 4, P_u 60 sK_u 0.9, P_u 600 s (temperature loop)

Results

Compared with Ziegler–Nichols, Tyreus–Luyben uses about 0.7 times the gain (Ku/3.2 against Ku/2.2 for PI, Ku/2.2 against 0.6Ku for PID) and an integral time 2.6 times (PI) to 4.4 times (PID) longer: less overshoot and better robustness for process loops. Ideal (parallel) PID form.

PI gain0.28125
PI integral time1,320.0s
PID gain0.40909
PID integral time1,320.0s
PID derivative time95.238s

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: K_u 4, P_u 60 s. The inputs, in the units selected above:

InputValue
Ultimate gain4.0000 -
Ultimate period60.000 s

Applying the formula below gives:

ResultValue
PI gain1.2500
PI integral time132.00 s
PID gain1.8182
PID integral time132.00 s
PID derivative time9.5238 s

Open this example in the calculator and change any input.

Formula

\(K_c = \frac{K_u}{3.2},\ T_i = 2.2P_u\ \text{(PI)}; \quad K_c = \frac{K_u}{2.2},\ T_i = 2.2P_u,\ T_d = \frac{P_u}{6.3}\ \text{(PID)}\)

Variables

Symbol Meaning SI unit
\(K_u\) Ultimate gain -
\(P_u\) Ultimate period s
\(K_{c,PI}\) PI gain -
\(T_{i,PI}\) PI integral time s
\(K_{c,PID}\) PID gain -
\(T_{i,PID}\) PID integral time s
\(T_{d,PID}\) PID derivative time s

Method and standards

Tyreus–Luyben rules.

Where it is used

  • Temperature, level and pressure loops.
  • After a relay auto-tune.

Common mistakes

  • Applying ideal-form settings to a series controller.
  • Testing at an unrepresentative load.

Assumptions and limits

  • Self-regulating loops.

References

  • Tyreus and Luyben (1992)
  • Ind. Eng. Chem. Res. 31: 2625; Seborg
  • Edgar
  • Mellichamp and Doyle
  • Process Dynamics and Control
  • 4th ed. (Wiley, 2016)
  • ch. 12

Questions and answers

How do I get K_u and P_u?

From a relay (auto-tune) test, or by raising P-only gain until the loop oscillates steadily.

Why not Ziegler–Nichols?

Z–N gives quarter-amplitude decay, too aggressive for most process loops.

What do the defaults represent?

An ultimate gain of 4 and a 60 s ultimate period.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.