FireCADCalc

Tank Level Process Dynamics: Integrating Rate and Residence Time

Integrating rate of a tank level loop from valve capacity, tank area and level span, with the residence time and the time to sweep the span.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationDistillery and ethanolRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: 3 m² tank, 2 m span, 20 m³/h valveDeaerator 25 m², 1 m span, 150 m³/h

Results

k' = Q_max/(A·L_s): with level and valve in %, 100 % valve imbalance moves the level 100 % in 1/k' seconds.

Integrating rate (%/s per % of valve)0.0016671/s
Time to change the span at full valve imbalance10.000min
Residence time at normal throughput12.000min

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 3 m² tank, 2 m span, 20 m³/h valve. The inputs, in the units selected above:

InputValue
Inflow change for 100 % valve20.000 m³/h
Tank cross-section3.0000 m²
Level transmitter span2.0000 m
Working volume (for residence time)6.0000 m³
Normal throughput10.000 m³/h

Applying the formula below gives:

ResultValue
Integrating rate (%/s per % of valve)9.2593e-04 1/s
Time to change the span at full valve imbalance18.000 min
Residence time at normal throughput36.000 min

Open this example in the calculator and change any input.

Formula

\(k' = \frac{Q_{max}}{AL_s}, \quad t_{fill} = \frac{1}{k'}, \quad \tau_r = \frac{V}{Q_n}\)

Variables

Symbol Meaning SI unit
\(Q_{max}\) Inflow change for 100 % valve m³/s
\(A\) Tank cross-section m²
\(L_s\) Level transmitter span m
\(V\) Working volume (for residence time) m³
\(Q_n\) Normal throughput m³/s
\(k'\) Integrating rate (%/s per % of valve) 1/s
\(t_{fill}\) Time to change the span at full valve imbalance s
\(\tau_r\) Residence time at normal throughput s

Method and standards

Tank mass balance.

Where it is used

  • Level loop tuning.
  • Choosing tank sizes for surge capacity.

Common mistakes

  • Using diameter for area.
  • Spans in different units.

Assumptions and limits

  • Constant cross-section.

References

  • Mass balance of a tank (Seborg, Edgar, Mellichamp and Doyle, Process Dynamics and Control, 4th ed. (Wiley, 2016), ch. 2)

Questions and answers

Why is level integrating?

Level changes at the rate of in-minus-out flow; it keeps changing as long as there is an imbalance.

How is k' measured?

Put the controller in manual, step the valve a few per cent and measure the slope of the level trend.

What do the defaults represent?

A 3 m² tank with a 2 m level span and a 20 m³/h valve.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators