Worked example
Example: Gain 2, 60 s, 10 s dead time, tc = theta. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Process gain (change in output / change in controller output) | 2.0000 - |
| Process time constant | 60.000 s |
| Dead time | 10.000 s |
| Desired closed-loop time constant | 10.000 s |
Applying the formula below gives:
| Result | Value |
|---|---|
| Controller gain | 1.5000 |
| Integral time | 60.000 s |
| Proportional band 1/K_c | 66.667 % |
| Integral gain (repeats per second × gain) | 0.025000 Hz |
Open this example in the calculator and change any input.
Formula
\(K_c = \frac{1}{K_p}\, \frac{\tau}{\tau_c + \theta}, \quad \tau_I = \min\left[\tau,\ 4(\tau_c + \theta)\right]\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(K_p\) | Process gain (change in output / change in controller output) | - |
| \(\tau\) | Process time constant | s |
| \(\theta\) | Dead time | s |
| \(\tau_c\) | Desired closed-loop time constant | s |
| \(K_c\) | Controller gain | - |
| \(\tau_I\) | Integral time | s |
| \(PB\) | Proportional band 1/K_c | - |
| \(K_c/\tau_I\) | Integral gain (repeats per second × gain) | 1/s |
Method and standards
SIMC rules from the IMC design for a first-order plus dead-time model.
Where it is used
- Tuning flow, pressure and temperature loops.
- Commissioning.
Common mistakes
- Controller gain in the wrong units.
- Using τ_c much below θ.
Assumptions and limits
- First-order plus dead-time model; PI settings only. The SIMC derivative setting for second-order (dominant lag) models is not given here.
References
- S. Skogestad
- Simple analytic rules for model reduction and PID controller tuning
- J. Process Control 13 (2003) 291
Questions and answers
Gain 2, time constant 60 s, dead time 10 s: what PI settings?
With τ_c = θ = 10 s: K_c = 60/(2 × 20) = 1.5 and τ_I = min(60, 80) = 60 s.
What does τ_c do?
It sets how fast the loop responds; larger τ_c is gentler and more robust.
Why the 4(τ_c + θ) limit?
For slow processes it stops the integral time growing so large that disturbances linger.