Worked example
Example: Level 0.01 %/s per %, θ 5 s. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Integrating rate (% PV per % output, per unit time) | 0.010000 1/s |
| Dead time | 5.0000 s |
| Closed-loop time constant (default = dead time) | 5.0000 s |
Applying the formula below gives:
| Result | Value |
|---|---|
| Controller gain | 10.000 |
| Integral time | 40.000 s |
| Approximate arrest time 2(τ_c + θ) (rule of thumb) | 20.000 s |
Open this example in the calculator and change any input.
Formula
\(K_c = \frac{1}{k'(\tau_c + \theta)}, \quad T_i = 4(\tau_c + \theta), \quad t_{arrest} \approx 2(\tau_c + \theta)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(k'\) | Integrating rate (% PV per % output, per unit time) | 1/s |
| \(\theta\) | Dead time | s |
| \(\tau_c\) | Closed-loop time constant (default = dead time) | s |
| \(K_c\) | Controller gain | - |
| \(T_i\) | Integral time | s |
| \(t_{arrest}\) | Approximate arrest time 2(τ_c + θ) (rule of thumb) | s |
Method and standards
SIMC rule.
Where it is used
- Drum, deaerator and tank level loops.
- Averaging level control.
Common mistakes
- Fast integral on level (cycling).
- Measuring k' in engineering units then using % gain.
Assumptions and limits
- Pure integrator with dead time.
- k' is a rate (per second, or per minute with the unit chosen); a rate read per minute and entered as per second would make K_c 60 times too small.
- The arrest time 2(τ_c + θ) is a rule-of-thumb estimate, not part of the SIMC rules.
References
- Skogestad (2003)
- J. Process Control 13: 291 (SIMC rules, integrating processes: K_c = 1/(k'(τ_c + θ)), T_i = 4(τ_c + θ))
Questions and answers
Why are level loops different?
Level has no natural steady state: any mismatch between in- and outflow ramps it. Integral action must be slow or the loop oscillates.
What is arrest time?
How long the controller takes to stop a level ramp after a step disturbance.
What do the defaults represent?
A level ramping 0.01 %/s per % valve with 5 s dead time.