Worked example
Example: Six bins, supply 13 °C, changeover 24 °C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Bin 1: mean outdoor temperature | 8.0000 °C |
| Bin 1: hours | 600.00 h |
| Bin 2: mean outdoor temperature | 14.000 °C |
| Bin 2: hours | 1,300.0 h |
| Bin 3: mean outdoor temperature | 19.000 °C |
| Bin 3: hours | 1,700.0 h |
| Bin 4: mean outdoor temperature | 24.000 °C |
| Bin 4: hours | 2,000.0 h |
| Bin 5: mean outdoor temperature | 29.000 °C |
| Bin 5: hours | 2,100.0 h |
| Bin 6: mean outdoor temperature | 34.000 °C |
| Bin 6: hours | 1,060.0 h |
| Supply air temperature | 13.000 °C |
| Changeover limit (outdoor air no warmer than this) | 24.000 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Full free cooling (outdoor at or below supply) | 600.00 h |
| Partial free cooling (between supply and changeover) | 5,000.0 h |
| Total hours in the bins | 8,760.0 h |
| Share of hours with some free cooling | 63.927 % |
Open this example in the calculator and change any input.
Formula
\(t_f = \sum_{T_i \le T_s} t_i, \quad t_p = \sum_{T_s < T_i \le T_{co}} t_i\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(T_{1}\) | Bin 1: mean outdoor temperature | K |
| \(t_{1}\) | Bin 1: hours | s |
| \(T_{2}\) | Bin 2: mean outdoor temperature | K |
| \(t_{2}\) | Bin 2: hours | s |
| \(T_{3}\) | Bin 3: mean outdoor temperature | K |
| \(t_{3}\) | Bin 3: hours | s |
| \(T_{4}\) | Bin 4: mean outdoor temperature | K |
| \(t_{4}\) | Bin 4: hours | s |
| \(T_{5}\) | Bin 5: mean outdoor temperature | K |
| \(t_{5}\) | Bin 5: hours | s |
| \(T_{6}\) | Bin 6: mean outdoor temperature | K |
| \(t_{6}\) | Bin 6: hours | s |
| \(T_s\) | Supply air temperature | K |
| \(T_{co}\) | Changeover limit (outdoor air no warmer than this) | K |
| \(t_f\) | Full free cooling (outdoor at or below supply) | s |
| \(t_p\) | Partial free cooling (between supply and changeover) | s |
| \(t\) | Total hours in the bins | s |
| \(x\) | Share of hours with some free cooling | - |
Method and standards
Bin counting.
Where it is used
- Control room and data room AHUs.
- Energy-saving cases.
Common mistakes
- Using monthly means.
- Ignoring humidity.
Assumptions and limits
- Bin mean temperatures; bins that add up to more than a year are flagged.
References
- Bin method on dry-bulb temperature (ASHRAE Handbook—HVAC Applications, economisers)
Questions and answers
What do the default bins give?
600 h of full free cooling and 5,000 h of partial out of 8,760.
Why partial?
Outdoor air cooler than the changeover limit still saves cooling, though it must be cooled further.
Humid climates?
Use an enthalpy changeover or the latent load rises.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.