Worked example
Example: 10 kg/h at 30 °C, 55 %, supply 8 g/kg. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Moisture load | 10.000 kg/h |
| Room temperature | 30.000 °C |
| Room relative humidity to hold | 55.000 % |
| Supply air humidity ratio | 8.0000 g/kg |
| Barometric pressure | 101.33 kPa |
Applying the formula below gives:
| Result | Value |
|---|---|
| Room humidity ratio | 14.675 g/kg |
| Dry air flow | 0.41616 kg/s |
| Air flow at room conditions | 1,317.0 m³/h |
| Latent capacity (at 2 501 kJ/kg, the psychrometric convention) | 6.9472 kW |
Open this example in the calculator and change any input.
Formula
\(\dot m_a = \frac{\dot m_w}{W_r - W_s}, \quad Q_l = \dot m_wh_{fg}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m_w\) | Moisture load | kg/s |
| \(t_r\) | Room temperature | K |
| \(\varphi_r\) | Room relative humidity to hold | - |
| \(W_s\) | Supply air humidity ratio | kg/kg |
| \(p\) | Barometric pressure | Pa |
| \(W_r\) | Room humidity ratio | kg/kg |
| \(\dot m_a\) | Dry air flow | kg/s |
| \(\dot V\) | Air flow at room conditions | m³/s |
| \(Q_l\) | Latent capacity (at 2 501 kJ/kg, the psychrometric convention) | W |
Method and standards
Moisture balance.
Where it is used
- Pool halls, stores, packing rooms.
- Desiccant and coil dehumidifier selection.
Common mistakes
- Ignoring infiltration moisture.
- Room RH set below what the supply can achieve.
Assumptions and limits
- Steady state; well-mixed room.
- Latent capacity at h_fg = 2 501 kJ/kg, the latent heat at 0 °C used in psychrometric load formulas; the condensation enthalpy at room temperature is about 2 % lower (about 2 430 kJ/kg at 30 °C).
References
- ASHRAE Handbook—Fundamentals (2017)
- ch. 1 (moisture balance)
Questions and answers
How do I find the moisture load?
Add people, open water (pool evaporation), wet processes, infiltration and product drying.
Why does supply dryness matter?
The drier the supply, the less air is needed to carry away the same moisture.
What do the defaults represent?
A 10 kg/h moisture load in a warm room held at 55 %, with supply air at 8 g/kg.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.