Solar Water Heater: Collector Area for Daily Hot Water

Collector area of a solar water heater for a daily hot water volume from cold and hot temperatures, daily solar radiation on the collector and system efficiency.

Refinery and petrochemicalChemical and fertiliserFood, dairy and textileIAPWS-IF97 (water and steam)

Inputs

Examples: 2000 L/day, 20 to 60 °C, 5.5 kWh/m²Hostel 5000 L/day, 25 to 55 °C, 4.8 kWh/m²

In kWh/m² per day, from your site's radiation data. Data in MJ/m² per day must be divided by 3.6 first.

Results

Size on the radiation of the month you design for; winter needs more area or backup heat.

Heat per day92.725kWh
Collector area37.465m²

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 2000 L/day, 20 to 60 °C, 5.5 kWh/m². The inputs, in the units selected above:

InputValue
Hot water per day2,000.0 L
Cold water temperature20.000 °C
Hot water temperature60.000 °C
Daily solar radiation on the collector plane (kWh/m² per day)5.5000 -
Average system efficiency45.000 %

Applying the formula below gives:

ResultValue
Heat per day92.725 kWh
Collector area37.465 m²

Open this example in the calculator and change any input.

Formula

\(A = \frac{\rho V (h_h - h_c)}{\eta H}\)

Variables

Symbol Meaning SI unit
\(V\) Hot water per day m³
\(T_c\) Cold water temperature K
\(T_h\) Hot water temperature K
\(H\) Daily solar radiation on the collector plane, in kWh/m² per day -
\(\rho\) Density of the cold water (IF97) kg/m³
\(h_h, h_c\) Enthalpy of the hot and cold water at 3 bar(a) (IF97) J/kg
\(\eta\) Average system efficiency -
\(Q\) Heat per day J
\(A\) Collector area m²

Method and standards

Energy balance.

Where it is used

  • Colony, hostel and canteen hot water.
  • Boiler feed pre-heating.

Common mistakes

  • Peak instead of daily radiation.
  • Horizontal radiation for tilted collectors.

Assumptions and limits

  • Daily average.
  • H is entered as a number in kWh/m² per day; radiation tables in MJ/m² per day must be divided by 3.6 first, otherwise the area comes out 3.6 times too small.

References

  • Energy balance A = Q/(ηH); water enthalpies from IAPWS-IF97

Questions and answers

2000 L/day from 20 to 60 °C at 5.5 kWh/m²/day, 45 %?

About 93 kWh a day: roughly 37.5 m² of collector.

What efficiency?

System average over the day, including tank and pipe losses.

Cloudy days?

Keep an electric or steam backup.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.