Worked example
Example: Glycol 100 kW, 4 K. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Cooling load | 100.00 kW |
| Coolant temperature range | 4.0000 K |
| Coolant density | 1,050.0 kg/m³ |
| Coolant specific heat | 3.6000 kJ/(kg·K) |
Applying the formula below gives:
| Result | Value |
|---|---|
| Mass flow | 25,000 kg/h |
| Volume flow | 23.810 m³/h |
| Flow relative to water (4186 J/kg K, 1000 kg/m³) | 1.1074 |
Open this example in the calculator and change any input.
Formula
\(\dot m = \frac{\dot Q}{c_p \Delta T}, \quad \dot V = \frac{\dot m}{\rho}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot Q\) | Cooling load | W |
| \(\Delta T\) | Coolant temperature range | K |
| \(\rho\) | Coolant density | kg/m³ |
| \(c_p\) | Coolant specific heat | J/(kg·K) |
| \(\dot m\) | Mass flow | kg/s |
| \(\dot V\) | Volume flow | m³/s |
| \(\dot V/\dot V_w\) | Flow relative to water (4186 J/kg K, 1000 kg/m³) | - |
Method and standards
Energy balance.
Where it is used
- Glycol chillers and cold stores.
- Brine ice plants.
Common mistakes
- Water properties for glycol.
- Properties at the wrong concentration.
Assumptions and limits
- Constant properties.
References
- Energy balance ṁ = Q/(c_p ΔT)
Questions and answers
100 kW with a 4 K range, ρ 1050, c_p 3600?
About 25,000 kg/h, 23.8 m³/h: 11 % more than water.
Why more flow than water?
Glycol mixes have lower specific heat.
Pump power?
Rises further because glycol is more viscous.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.