Worked example
Example: 2000 L, 15 to 60 °C, 24 kW. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Tank volume | 2,000.0 L |
| Starting temperature | 15.000 °C |
| Final temperature | 60.000 °C |
| Heater power (input) | 24.000 kW |
| Heater efficiency (including losses) | 95.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Water mass (density at the start) | 1,998.4 kg |
| Heat to the water | 104.43 kWh |
| Energy input | 109.92 kWh |
| Heat-up time | 4.5801 h |
Open this example in the calculator and change any input.
Formula
\(Q = m(h_2 - h_1), \quad t = \frac{Q}{\eta P}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V\) | Tank volume | m³ |
| \(T_1\) | Starting temperature | K |
| \(T_2\) | Final temperature | K |
| \(P\) | Heater power (input) | W |
| \(\eta\) | Heater efficiency (including losses) | - |
| \(m\) | Water mass (density at the start) | kg |
| \(Q\) | Heat to the water | J |
| \(E\) | Energy input | J |
| \(t\) | Heat-up time | s |
Method and standards
Energy balance.
Where it is used
- Colony and canteen hot water.
- Process water heating.
Common mistakes
- Litres taken as kg at high temperature.
- Ignoring standing losses.
Assumptions and limits
- Fully mixed tank.
References
- Q = m (h₂ − h₁) with IAPWS-IF97 enthalpies
Questions and answers
2000 L from 15 to 60 °C with 24 kW?
About 104 kWh of heat: roughly 4.6 h at 95 %.
Why use enthalpy, not 4.186 kJ/kg K?
It is the same within a fraction of a per cent here; the IF97 route is exact.
Steam coil heaters?
Enter the coil duty as the power.