Worked example
Example: Chilled water 120 m³/h in DN150. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Water flow | 120.00 m³/h |
| Pipe inside diameter | 154.10 mm |
| Pipe length, supply and return | 400.00 m |
| Pipe roughness | 0.045000 mm |
| Sum of fitting loss coefficients | 40.000 - |
| Equipment drops (chiller, coil, valve, strainer) | 150.00 kPa |
| Water temperature | 10.000 °C |
| Pump and motor efficiency | 65.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Velocity | 1.7872 m/s |
| Reynolds number | 210,935 |
| Darcy friction factor | 0.017563 |
| Pipe and fittings | 136.68 kPa |
| Pump head | 29.236 m |
| Electrical power | 14.702 kW |
Open this example in the calculator and change any input.
Formula
\(H = \frac{(f L/D + \Sigma K)\rho v^2/2 + \Delta p_e}{\rho g}, \quad P = \frac{\rho g \dot V H}{\eta}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot V\) | Water flow | m³/s |
| \(D\) | Pipe inside diameter | m |
| \(L\) | Pipe length, supply and return | m |
| \(\varepsilon\) | Pipe roughness | m |
| \(\Sigma K\) | Sum of fitting loss coefficients | - |
| \(\Delta p_e\) | Equipment drops (chiller, coil, valve, strainer) | Pa |
| \(T\) | Water temperature | K |
| \(\eta\) | Pump and motor efficiency | - |
| \(v\) | Velocity | m/s |
| \(Re\) | Reynolds number | - |
| \(f\) | Darcy friction factor | - |
| \(\Delta p_p\) | Pipe and fittings | Pa |
| \(H\) | Pump head | m |
| \(P\) | Electrical power | W |
Method and standards
Darcy–Weisbach.
Where it is used
- Chilled and hot water pump selection.
- Cooling water loops.
Common mistakes
- Adding static height.
- Using only one way of the loop.
Assumptions and limits
- Single index circuit, steady flow.
References
- Darcy–Weisbach with Colebrook friction; water properties IAPWS-IF97 and IAPWS 2008 viscosity
Questions and answers
120 m³/h in DN150, 400 m, ΣK 40, 150 kPa of equipment?
About 1.8 m/s; roughly 29 m of head and 15 kW.
Why no static head?
In a closed loop the water column on the way up balances the way down.
Index circuit?
Use the path with the highest drop; other branches are balanced to it.