FireCADCalc

Chiller Energy over a Year from Part-Load kW/TR

Yearly chiller electricity and cost from the rated capacity and four part-load bins of hours and kW/TR, with the weighted average kW/TR.

Refinery and petrochemicalChemical and fertiliserFood, dairy and textile

Inputs

Examples: 500 TR office plantProcess chiller 200 TR, mostly full

Bin 1

Bin 2

Bin 3

Bin 4

Results

Use kW/TR from the maker's part-load data at your condenser water temperatures, and include pumps and tower fans separately.

Cooling delivered1,475,000TR·h
Electricity946,000kWh
Average kW/TR0.64136
Cost6,622,000

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 500 TR office plant. The inputs, in the units selected above:

InputValue
Rated capacity500.00 TR
Bin 1: load share100.00 %
Bin 1: hours500.00 h
Bin 1: kW/TR0.62000 -
Bin 2: load share75.000 %
Bin 2: hours2,000.0 h
Bin 2: kW/TR0.55000 -
Bin 3: load share50.000 %
Bin 3: hours2,500.0 h
Bin 3: kW/TR0.50000 -
Bin 4: load share25.000 %
Bin 4: hours1,000.0 h
Bin 4: kW/TR0.60000 -
Electricity price per kWh8.0000 -

Applying the formula below gives:

ResultValue
Cooling delivered1,750,000 TR·h
Electricity955,000 kWh
Average kW/TR0.54571
Cost7,640,000

Open this example in the calculator and change any input.

Formula

\(E = \sum_i \frac{x_i \dot Q_r}{TR}\, e_i\, t_i\)

Variables

Symbol Meaning SI unit
\(\dot Q_r\) Rated capacity W
\(x_{1}\) Bin 1: load share -
\(t_{1}\) Bin 1: hours s
\(e_{1}\) Bin 1: kW/TR -
\(x_{2}\) Bin 2: load share -
\(t_{2}\) Bin 2: hours s
\(e_{2}\) Bin 2: kW/TR -
\(x_{3}\) Bin 3: load share -
\(t_{3}\) Bin 3: hours s
\(e_{3}\) Bin 3: kW/TR -
\(x_{4}\) Bin 4: load share -
\(t_{4}\) Bin 4: hours s
\(e_{4}\) Bin 4: kW/TR -
\(c\) Electricity price per kWh -
\(Q\) Cooling delivered J
\(E\) Electricity J
\(\bar e\) Average kW/TR -
\(C\) Cost -

Method and standards

Bin method.

Where it is used

  • Chiller selection and savings cases.
  • Energy budgets.

Common mistakes

  • Leaving out auxiliaries.
  • Rated kW/TR at all loads.

Assumptions and limits

  • Constant efficiency within each bin.
  • Bin hours adding up to more than a year are flagged.

References

  • Bin method E = Σ TR × kW/TR × hours

Questions and answers

500 TR with the default bins?

About 955,000 kWh a year at about 0.55 kW/TR on average.

Where do the bins come from?

Your load profile: hours at each load band from logs or a building model.

Why not just use IPLV?

IPLV uses national-average weights; your hours are what you pay for.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.