FireCADCalc

Chiller IPLV from Part-Load Efficiencies (AHRI 550/590 Weights)

Integrated part load value (IPLV) of a chiller from its efficiency at 100, 75, 50 and 25 % load with the AHRI 550/590 weights, as COP, EER and kW/TR.

Refinery and petrochemicalChemical and fertiliserFood, dairy and textile

Inputs

Examples: CentrifugalAir-cooled screw

Results

Weights 1, 42, 45 and 12 % at the AHRI rating conditions; AHRI warns IPLV is not a site energy prediction.

IPLV as COP3.9120
IPLV as kW/TR0.89899
IPLV as EER (Btu/h per W)13.348

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Centrifugal. The inputs, in the units selected above:

InputValue
COP at 100 % load6.1000 -
COP at 75 % load7.2000 -
COP at 50 % load8.4000 -
COP at 25 % load7.0000 -

Applying the formula below gives:

ResultValue
IPLV as COP7.7050
IPLV as kW/TR0.45644
IPLV as EER (Btu/h per W)26.291

Open this example in the calculator and change any input.

Formula

\(IPLV = 0.01A + 0.42B + 0.45C + 0.12D, \quad IPLV_{kW/TR} = \frac{1}{0.01/k_A + 0.42/k_B + 0.45/k_C + 0.12/k_D}, \quad k_i = \frac{3.517}{COP_i}\)

Variables

Symbol Meaning SI unit
\(A\) COP at 100 % load -
\(B\) COP at 75 % load -
\(C\) COP at 50 % load -
\(D\) COP at 25 % load -
\(IPLV\) IPLV as COP -
\(IPLV_{kW/TR}\) IPLV as kW/TR -
\(k_A \ldots k_D\) Part-load efficiencies as kW/TR, 3.517/COP -
\(IPLV_{EER}\) IPLV as EER (Btu/h per W) -

Method and standards

AHRI weighting.

Where it is used

  • Comparing chiller offers.
  • Energy code checks.

Common mistakes

  • Weighting kW/TR arithmetically.
  • Ratings at non-standard conditions.

Assumptions and limits

  • AHRI rating conditions.

References

  • AHRI Standard 550/590 IPLV weights 0.01
  • 0.42
  • 0.45
  • 0.12 (COP weighted mean; kW/TR weighted harmonic mean)

Questions and answers

COP 6.1, 7.2, 8.4 and 7.0?

IPLV about 7.7 as COP, 0.46 kW/TR.

Why weight 50 % load most?

Chillers spend most hours there in the national-average building.

Use it for my plant's energy?

No; use your own load profile with the part-load energy calculator.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.