Worked example
Example: DN150 at 7 °C, 40 mm, 35 °C 70 %. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Pipe outer diameter | 168.30 mm |
| Insulation thickness | 40.000 mm |
| Insulation conductivity | 0.035000 W/(m·K) |
| Chilled water or brine temperature | 7.0000 °C |
| Ambient air temperature | 35.000 °C |
| Ambient relative humidity | 70.000 % |
| Surface emissivity | 90.000 % |
| Pipe length | 200.00 m |
| Water flow | 72,000 kg/h |
| Specific heat of the water or brine | 4.1860 kJ/(kg·K) |
Applying the formula below gives:
| Result | Value |
|---|---|
| Heat gain per metre | 14.531 W/m |
| Total heat gain | 2.9062 kW |
| Outer surface temperature | 32.697 °C |
| Ambient dew point | 28.701 °C |
| Margin (negative: condensation) | 3.9961 K |
| Water temperature rise | 0.034714 K |
Open this example in the calculator and change any input.
Formula
\(q' = \frac{T_a - T_w}{\frac{\ln(D/D_o)}{2\pi\lambda} + \frac{1}{h_{se}\pi D}}, \quad \Delta T_w = \frac{q' L}{\dot m c_p}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(D_o\) | Pipe outer diameter | m |
| \(s\) | Insulation thickness | m |
| \(\lambda\) | Insulation conductivity | W/(m·K) |
| \(T_w\) | Chilled water or brine temperature | K |
| \(T_a\) | Ambient air temperature | K |
| \(\varphi\) | Ambient relative humidity | - |
| \(\varepsilon\) | Surface emissivity | - |
| \(L\) | Pipe length | m |
| \(\dot m\) | Water flow | kg/s |
| \(c_p\) | Specific heat of the water or brine | J/(kg·K) |
| \(q'\) | Heat gain per metre | W/m |
| \(\dot Q\) | Total heat gain | W |
| \(T_s\) | Outer surface temperature | K |
| \(T_{dp}\) | Ambient dew point | K |
| \(T_s - T_{dp}\) | Margin (negative: condensation) | K |
| \(\Delta T_w\) | Water temperature rise | K |
Method and standards
ISO 12241 conduction and surface coefficient.
Where it is used
- Chilled water mains in plant rooms and pipe racks.
- Insulation checks.
Common mistakes
- No vapour barrier.
- Indoor still-air coefficient used outdoors in wind.
Assumptions and limits
- Still air, steady state.
- The water temperature rise uses the specific heat entered (4186 J/(kg·K) for water; lower for glycol and brine).
References
- ISO 12241 insulated pipe method (engine InsulatedPipe); dew point over water or ice from IAPWS; water rise with the c_p entered
Questions and answers
DN150 at 7 °C with 40 mm insulation in 35 °C, 70 % air?
About 14.5 W/m of gain; the surface is about 4 K above the 28.7 °C dew point.
Why does a thin layer sweat?
Its surface runs too close to the pipe temperature.
Vapour barrier?
Essential: moisture in the insulation ruins it, however thick.