Worked example
Example: 2.5 m³/h, 10 kPa, Kvs 4. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Design flow | 2.5000 m³/h |
| Pressure drop to absorb | 10.000 kPa |
| Specific gravity | 1.0000 - |
| Kvs of the selected valve (fully open), metric | 4.0000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Kv required | 7.9057 |
| Pressure drop of the selected valve fully open | 39.062 kPa |
| Kv fraction to set | 197.64 % |
Open this example in the calculator and change any input.
Formula
\(K_v = \dot V\sqrt{\frac{SG}{\Delta p}}, \quad \Delta p_{open} = SG\left(\frac{\dot V}{K_{vs}}\right)^2\quad(\mathrm{m^3/h,\ bar})\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot V\) | Design flow | m³/s |
| \(\Delta p\) | Pressure drop to absorb | Pa |
| \(SG\) | Specific gravity | - |
| \(K_{vs}\) | Kvs of the selected valve (fully open), metric | - |
| \(K_v\) | Kv required | - |
| \(\Delta p_{open}\) | Pressure drop of the selected valve fully open | Pa |
| \(K_v/K_{vs}\) | Kv fraction to set | - |
Method and standards
K_v definition.
Where it is used
- Commissioning heating and chilled water.
- Selecting balancing valve sizes.
Common mistakes
- Valve so large it works almost closed.
- Mixing Kv and Cv.
Assumptions and limits
- Turbulent, non-flashing liquid.
- Kv and Kvs are metric (m³/h at 1 bar) in every unit system; convert a US Cv by Kv = Cv/1.156.
References
- K_v = Q√(SG/Δp)
- Q in m³/h and Δp in bar (IEC 60534 definition of K_v)
Questions and answers
Why balance a hydronic system?
Circuits near the pump get too much water and remote ones too little; balancing valves absorb the excess head.
How much pressure drop should a balancing valve take?
Enough to measure accurately (3 kPa or more) and to absorb the circuit's excess head.
What do the defaults represent?
A terminal circuit flow with a 10 kPa excess head and a mid-size valve.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.