Transformer Turns Ratio, Voltages and Currents

Turns ratio of a single- or three-phase transformer from the line voltages and winding connection (Dy, Yy, Dd, Yd), the secondary turns, and the rated line currents.

Thermal power plantProcess steam and utilitiesElectrician and wireman licence examinations

Inputs

Examples: 1 MVA 11 kV / 433 V Dyn11, 1 500 turns10 kVA single phase 230 / 24 V, 460 turns5 MVA 33 / 6.6 kV star–delta, 2 000 turns

Results

Ideal transformer at no load: the winding voltages are in the ratio of the turns. Star windings carry line voltage / √3; delta windings the full line voltage.

Line voltage ratio V₁ / V₂9.5833
Primary phase (winding) voltage230.00V
Secondary phase (winding) voltage24.000V
Turns ratio (winding voltages)9.5833
Secondary turns per phase48.000
Primary line current43.478A
Secondary line current416.67A

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 1 MVA 11 kV / 433 V Dyn11, 1 500 turns. The inputs, in the units selected above:

InputValue
Primary line voltage11.000 kV
Secondary line voltage433.00 V
Rated power1,000.0 kVA
Phases and connection (primary–secondary)Three phase, delta–star (Dy)
Primary turns per phase1,500.0 -

Applying the formula below gives:

ResultValue
Line voltage ratio V₁ / V₂25.404
Primary phase (winding) voltage11,000 V
Secondary phase (winding) voltage249.99 V
Turns ratio (winding voltages)44.001
Secondary turns per phase34.090
Primary line current52.486 A
Secondary line current1,333.4 A

Open this example in the calculator and change any input.

Formula

\(\frac{N_1}{N_2} = \frac{V_{p1}}{V_{p2}}, \quad V_p = V_L\ (\Delta), \ \frac{V_L}{\sqrt 3}\ (Y)\)

\(I_L = \frac{S}{\sqrt 3\, V_L}\ (3\phi), \quad \frac{S}{V}\ (1\phi)\)

Variables

Symbol Meaning SI unit
\(V_1\) Primary line voltage V
\(V_2\) Secondary line voltage V
\(S\) Rated power VA
\(\text{conn}\) Phases and connection (primary–secondary) -
\(N_1\) Primary turns per phase -
\(a_L\) Line voltage ratio V₁ / V₂ -
\(V_{p1}\) Primary phase (winding) voltage V
\(V_{p2}\) Secondary phase (winding) voltage V
\(N_1/N_2\) Turns ratio (winding voltages) -
\(N_2\) Secondary turns per phase -
\(I_1\) Primary line current A
\(I_2\) Secondary line current A

Method and standards

Ideal transformer: winding voltages in the turns ratio; star winding voltage is line voltage over √3.

Where it is used

  • Turns ratio test (TTR) acceptance.
  • Rewinding and checking nameplates.
  • Electrical examinations.

Common mistakes

  • Using line ratio as turns ratio for Dy or Yd.
  • Forgetting √3 in three-phase currents.

Assumptions and limits

  • N₂ is the exact value for the voltage ratio; a real winding has whole turns, so round it and accept the small voltage change (the page shows it), or adjust N₁.

  • No-load, ideal transformer.

References

  • Ideal transformer relations (IEC 60076-1 terminology)

Questions and answers

What is the turns ratio of an 11 kV / 433 V Dyn11 transformer?

44.0: the delta primary winding has 11 kV and the star secondary winding 250 V. With 1500 primary turns, 34 secondary turns.

Why not 11000 / 433 = 25.4?

That is the line voltage ratio; the winding (turns) ratio is between phase voltages and depends on star or delta.

What are the currents at 1 MVA?

52.5 A on the 11 kV side and 1333 A on the 433 V side.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.