Worked example
Example: 1 MVA 11 kV / 433 V Dyn11, 1 500 turns. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Primary line voltage | 11.000 kV |
| Secondary line voltage | 433.00 V |
| Rated power | 1,000.0 kVA |
| Phases and connection (primary–secondary) | Three phase, delta–star (Dy) |
| Primary turns per phase | 1,500.0 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Line voltage ratio V₁ / V₂ | 25.404 |
| Primary phase (winding) voltage | 11,000 V |
| Secondary phase (winding) voltage | 249.99 V |
| Turns ratio (winding voltages) | 44.001 |
| Secondary turns per phase | 34.090 |
| Primary line current | 52.486 A |
| Secondary line current | 1,333.4 A |
Open this example in the calculator and change any input.
Formula
\(\frac{N_1}{N_2} = \frac{V_{p1}}{V_{p2}}, \quad V_p = V_L\ (\Delta), \ \frac{V_L}{\sqrt 3}\ (Y)\)
\(I_L = \frac{S}{\sqrt 3\, V_L}\ (3\phi), \quad \frac{S}{V}\ (1\phi)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V_1\) | Primary line voltage | V |
| \(V_2\) | Secondary line voltage | V |
| \(S\) | Rated power | VA |
| \(\text{conn}\) | Phases and connection (primary–secondary) | - |
| \(N_1\) | Primary turns per phase | - |
| \(a_L\) | Line voltage ratio V₁ / V₂ | - |
| \(V_{p1}\) | Primary phase (winding) voltage | V |
| \(V_{p2}\) | Secondary phase (winding) voltage | V |
| \(N_1/N_2\) | Turns ratio (winding voltages) | - |
| \(N_2\) | Secondary turns per phase | - |
| \(I_1\) | Primary line current | A |
| \(I_2\) | Secondary line current | A |
Method and standards
Ideal transformer: winding voltages in the turns ratio; star winding voltage is line voltage over √3.
Where it is used
- Turns ratio test (TTR) acceptance.
- Rewinding and checking nameplates.
- Electrical examinations.
Common mistakes
- Using line ratio as turns ratio for Dy or Yd.
- Forgetting √3 in three-phase currents.
Assumptions and limits
N₂ is the exact value for the voltage ratio; a real winding has whole turns, so round it and accept the small voltage change (the page shows it), or adjust N₁.
No-load, ideal transformer.
References
- Ideal transformer relations (IEC 60076-1 terminology)
Questions and answers
What is the turns ratio of an 11 kV / 433 V Dyn11 transformer?
44.0: the delta primary winding has 11 kV and the star secondary winding 250 V. With 1500 primary turns, 34 secondary turns.
Why not 11000 / 433 = 25.4?
That is the line voltage ratio; the winding (turns) ratio is between phase voltages and depends on star or delta.
What are the currents at 1 MVA?
52.5 A on the 11 kV side and 1333 A on the 433 V side.