Worked example
Example: 50 Hz, 1.2 T, 150 cm², 2 750 and 108 turns. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Frequency | 50.000 Hz |
| Peak flux density in the core | 1.2000 T |
| Net core cross-section | 150.00 cm² |
| Primary turns | 2,750.0 - |
| Secondary turns | 108.00 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Peak flux B_m A_c | 18.000 mWb |
| Volts per turn | 3.9986 V |
| Primary EMF | 10,996 V |
| Secondary EMF | 431.85 V |
Open this example in the calculator and change any input.
Formula
\(E = \sqrt 2\, \pi f N \Phi_m \approx 4.44\, f N \Phi_m, \quad \Phi_m = B_m A_c\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(f\) | Frequency | 1/s |
| \(B_m\) | Peak flux density in the core | T |
| \(A_c\) | Net core cross-section | m² |
| \(N_1\) | Primary turns | - |
| \(N_2\) | Secondary turns | - |
| \(\Phi_m\) | Peak flux B_m A_c | Wb |
| \(E_t\) | Volts per turn | V |
| \(E_1\) | Primary EMF | V |
| \(E_2\) | Secondary EMF | V |
Method and standards
RMS value of N dΦ/dt for a sinusoidal flux.
Where it is used
- Winding design and rewinding.
- Electrical examinations.
Common mistakes
- Using RMS flux density.
- Gross instead of net core area.
Assumptions and limits
No saturation check beyond a warning above 1.9 T; grain-oriented silicon steel saturates at about 1.7–1.9 T.
Sinusoidal flux; no leakage.
References
- Faraday's law for sinusoidal flux: E = √2 π f N Φ_m
Questions and answers
What are the volts per turn at 50 Hz, 1.2 T and 150 cm²?
Flux 18 mWb: 3.999 V per turn.
How many turns for 11 kV?
About 2751.
Why does a 60 Hz transformer overheat on 50 Hz?
The same voltage needs 20 % more flux, which saturates the core.