FireCADCalc

Single-Tuned Harmonic Filter: Design and Harmonic Current Share

Capacitor, reactor and resistor reactances of a single-tuned filter from its effective kvar, tuning order and quality factor, and the harmonic current it absorbs.

Thermal power plantProcess steam and utilitiesChemical and fertiliser

Inputs

Examples: Illustrative 300 kvar 4.7 filter on 415 VSame filter, 7th harmonic11 kV 2 Mvar 4.8 filter

Accepted: 100 to 100,000 V
Accepted: 0.1 to 10,000 MVA
Accepted: 1 to 100,000 kvar
Accepted: 2 to 20
Accepted: 5 to 200
Accepted: 2 to 50
Accepted: 0 to 100,000 A

Results

X_C = (V²/Q_eff)·h_t²/(h_t² − 1), X_L = X_C/h_t², R = h_tX_L/Q_f; current divider at order h between j·hX_s and R + j(hX_L − X_C/h). Tune slightly below the target harmonic (4.7 for the 5th) so ageing capacitors and frequency drift do not push resonance onto it, and rate the capacitor for the fundamental voltage rise h_t²/(h_t² − 1) plus harmonics.

Capacitor reactance at fundamental0.60130Ω
Reactor reactance at fundamental0.027221Ω
Filter resistance0.003198Ω
Harmonic current into the filter21.926A
Harmonic current into the supply38.081A
Harmonic voltage at the bus0.95804%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 300 kvar 4.7 filter on 415 V. The inputs, in the units selected above:

InputValue
Bus line voltage415.00 V
Bus short-circuit power20.000 MVA
Filter effective kvar at fundamental300.00 kvar
Tuning order4.7000 -
Filter quality factor40.000 -
Harmonic order of the source current5.0000 -
Harmonic current from the load120.00 A

Applying the formula below gives:

ResultValue
Capacitor reactance at fundamental0.60130 Ω
Reactor reactance at fundamental0.027221 Ω
Filter resistance0.003198 Ω
Harmonic current into the filter87.594 A
Harmonic current into the supply32.880 A
Harmonic voltage at the bus0.59086 %

Open this example in the calculator and change any input.

Formula

\(X_C = \frac{V^2}{Q_{eff}}\frac{h_t^2}{h_t^2 - 1}, \quad X_L = \frac{X_C}{h_t^2}, \quad R = \frac{h_tX_L}{Q_f}, \quad I_{f,h} = I_h\frac{Z_s(h)}{Z_s(h) + Z_f(h)}\)

Variables

Symbol Meaning SI unit
\(V\) Bus line voltage V
\(S_{sc}\) Bus short-circuit power VA
\(Q_{eff}\) Filter effective kvar at fundamental var
\(h_t\) Tuning order -
\(Q_f\) Filter quality factor -
\(h\) Harmonic order of the source current -
\(I_h\) Harmonic current from the load A
\(X_C\) Capacitor reactance at fundamental Ω
\(X_L\) Reactor reactance at fundamental Ω
\(R\) Filter resistance Ω
\(I_{f,h}\) Harmonic current into the filter A
\(I_{s,h}\) Harmonic current into the supply A
\(V_h\) Harmonic voltage at the bus -

Method and standards

Filter design.

Where it is used

  • Harmonic mitigation for drives and rectifiers.
  • Checking filter overloading from other loads' harmonics.

Common mistakes

  • Ignoring harmonics imported from the supply.
  • Rating the capacitor at bus voltage.

Assumptions and limits

  • Inductive source at harmonics; one dominant harmonic.

References

  • Single-tuned filter design and current division

Questions and answers

Why tune to 4.7 rather than 5?

Capacitance falls with age and temperature, raising the tuned frequency; starting below the 5th keeps it from sitting exactly on the harmonic.

What quality factor is typical?

About 20–100 for reactors in single-tuned filters; lower Q widens the band but adds losses.

What do the defaults represent?

An illustrative 300 kvar filter tuned to 4.7 with Q 40 on a 415 V bus of 20 MVA fault level, absorbing a 120 A 5th harmonic.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Dugan, McGranaghan, Santoso and Beaty, Electrical Power Systems Quality, 3rd ed. (McGraw-Hill, 2012)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.