FireCADCalc

Wire Resistance from Length, Area and Material

Resistance of a copper, aluminium or other wire at 20 °C from its length and cross-section, with the voltage drop and power loss at a current.

Thermal power plantProcess steam and utilitiesElectrician and wireman licence examinations

Inputs

Examples: 100 m of 2.5 mm² copper at 16 A500 m of 185 mm² aluminium at 250 A10 m of 1 mm² nichrome (1.1 Ω·mm²/m) at 5 A

Used only when the conductor is 'Other'; ignored for copper and aluminium, which use their standard values.

Results

One conductor at 20 °C. A circuit has a go and a return conductor; resistance rises about 0.4 % per kelvin for copper and aluminium.

Resistivity used0.017241Ω·mm²/m
Resistance at 20 °C0.68966Ω
Voltage drop I R11.034V
Power loss I² R176.55W

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 100 m of 2.5 mm² copper at 16 A. The inputs, in the units selected above:

InputValue
ConductorCopper (annealed, IACS)
Resistivity at 20 °C (for other metals)0.10000 Ω·mm²/m
Length of wire100.00 m
Cross-section2.5000 mm²
Current16.000 A

Applying the formula below gives:

ResultValue
Resistivity used0.017241 Ω·mm²/m
Resistance at 20 °C0.68966 Ω
Voltage drop I R11.034 V
Power loss I² R176.55 W

Open this example in the calculator and change any input.

Formula

\(R = \frac{\rho\, L}{A}, \quad \Delta V = I R, \quad P = I^2 R\)

Variables

Symbol Meaning SI unit
\(\text{metal}\) Conductor -
\(\rho\) Resistivity at 20 °C (for other metals) Ω·m
\(L\) Length of wire m
\(A\) Cross-section m²
\(I\) Current A
\(\rho_{20}\) Resistivity used Ω·m
\(R\) Resistance at 20 °C Ω
\(\Delta V\) Voltage drop I R V
\(P\) Power loss I² R W

Method and standards

Resistance of a uniform conductor.

Where it is used

  • Checking cable and winding resistance.
  • Earth and bonding conductors.

Common mistakes

  • Using mm² as m².
  • Forgetting the return conductor.

Assumptions and limits

  • The resistivity input is used only for 'Other'; for copper and aluminium the standard values (IEC 60028 and IEC 60889) are used and the entered value is ignored. The value used is shown as an output.

  • DC resistance at 20 °C; no skin effect.

References

  • R = ρ L / A
  • IEC 60028 (annealed copper, 1/58 Ω·mm²/m)
  • IEC 60889 (aluminium, 28.264 nΩ·m)

Questions and answers

What is the resistance of 100 m of 2.5 mm² copper?

0.690 Ω at 20 °C; at 16 A it drops 11.0 V.

And aluminium?

1.131 Ω: about 1.64 times copper.

Is this the loop resistance?

No, one conductor; double it for go and return.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.