Worked example
Example: 100 m of 2.5 mm² copper at 16 A. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Conductor | Copper (annealed, IACS) |
| Resistivity at 20 °C (for other metals) | 0.10000 Ω·mm²/m |
| Length of wire | 100.00 m |
| Cross-section | 2.5000 mm² |
| Current | 16.000 A |
Applying the formula below gives:
| Result | Value |
|---|---|
| Resistivity used | 0.017241 Ω·mm²/m |
| Resistance at 20 °C | 0.68966 Ω |
| Voltage drop I R | 11.034 V |
| Power loss I² R | 176.55 W |
Open this example in the calculator and change any input.
Formula
\(R = \frac{\rho\, L}{A}, \quad \Delta V = I R, \quad P = I^2 R\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\text{metal}\) | Conductor | - |
| \(\rho\) | Resistivity at 20 °C (for other metals) | Ω·m |
| \(L\) | Length of wire | m |
| \(A\) | Cross-section | m² |
| \(I\) | Current | A |
| \(\rho_{20}\) | Resistivity used | Ω·m |
| \(R\) | Resistance at 20 °C | Ω |
| \(\Delta V\) | Voltage drop I R | V |
| \(P\) | Power loss I² R | W |
Method and standards
Resistance of a uniform conductor.
Where it is used
- Checking cable and winding resistance.
- Earth and bonding conductors.
Common mistakes
- Using mm² as m².
- Forgetting the return conductor.
Assumptions and limits
The resistivity input is used only for 'Other'; for copper and aluminium the standard values (IEC 60028 and IEC 60889) are used and the entered value is ignored. The value used is shown as an output.
DC resistance at 20 °C; no skin effect.
References
- R = ρ L / A
- IEC 60028 (annealed copper, 1/58 Ω·mm²/m)
- IEC 60889 (aluminium, 28.264 nΩ·m)
Questions and answers
What is the resistance of 100 m of 2.5 mm² copper?
0.690 Ω at 20 °C; at 16 A it drops 11.0 V.
And aluminium?
1.131 Ω: about 1.64 times copper.
Is this the loop resistance?
No, one conductor; double it for go and return.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.